Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
!
Warning!
Inoperable, unsupervised devices!
Be sure the count of devices displayed when this operation completes matches the number of
devices installed on both buses. Devices not detected during the update bus operation will
not operate and will not be supervised.
i
Notice!
These menu items are allowed only at the local keypad.
The following window appears:
OPTION BUS (M/M)
1 - UPDATE BUS
2 - SETUP KEYPDS
Press [1] to program the system to update the bus. After you program Update Bus, the
following window appears:
UPDATE COMPLETE
TOT BUS DEVS: X
Then the previous window appears.
Setup keypads
Shortcut: 0-PROG, 3-PROG SYSTEM, 4-OPTION BUS
This feature tells the system how many keypads to supervise. It automatically performs an
update bus operation as it completes.
OPTION BUS
1 - UPDATE BUS
2 - SETUP KEYPDS
Press [2] to set up keypads. The following window appears:
# OF KEYPADS (__)
(0-4):_______
Enter the desired value and press [#/Enter]. The existing setting is shown in parentheses on
the first line. After you set up the keypads, the update bus operation proceeds, then the
previous window appears.
PIN required
Local
Shortcut: 0-PROG, 3-PROG SYSTEM, 5-PIN REQUIRED?
A PIN can be required before performing operations. Enter the PIN at the local or built-in
keypad.
The following window appears:
8.3.4
Fire Alarm Control Panels Control Panel Programming | en 65