When the scanning is completed, the FPD‑7024 checks for missing devices. Missing devices
are addresses with no devices on the multiplex buses, but are programmed into the
FPD‑7024’s site-specific memory area. If missing devices are detected, the FPD‑7024 shows
the following menu (where xxx is the address of the first point of the missing device):
MISSING PT @ xxx
0- DELETE POINT
1- KEEP POINT
2- DEL REMAIN
3- KEEP REMAIN
DELETE POINT: If selected, the missing point and any addresses it implemented (up to eight
for an octal input module) are permanently deleted from the site specific memory area. If the
deleted device is an I/O module, the output zones that were programmed for the relay are
reset to 0. If additional devices are found to be missing, the above display is repeated for each
missing device.
KEEP POINT: If selected, the FPD‑7024 retains the programming for the existing point and
continues scanning for additional missing points.
DEL REMAIN: If selected, the following prompt # KEY TO CONFIRM appears at the FPD‑7024.
If the [#/Enter] key is pressed, all the missing points are deleted from the site-specific memory
area and the auto program process continues with the devices found menu. If any other key is
pressed, the existing point is kept and the control panel continues scanning for additional
missing devices.
KEEP REMAIN: If selected, no additional points are deleted and the auto program process
continues with the Devices Found menu. Points individually deleted with the Delete Point
command before selecting the Keep Remain command stay deleted when Keep Remain is
selected.
!
Warning!
Missing points!
Use the DEL REMAINING feature with caution. Any devices missing from the multiplex buses
during the DEL REMAINING operation, even momentarily, are permanently deleted. These
points do not operate, and do not generate trouble conditions even if they are returned to the
bus.
When the delete point operation is finished, the FPD‑7024 shows for five seconds the total
number of points that were deleted from the control panel (xxx indicates the number of points
that were removed from the control panel’s site specific configuration).
AUTO PROGRAM
xxx POINTS DELETED
Confirm that only the expected number of points was removed from the system. Points that
are removed from the control panel’s site-specific configuration do not operate and are not
supervised even if they are returned to the bus.
When the point delete process completes, the auto programming process automatically
checks for new devices on the buses. New devices are found when a device is present on one
of the multiplex buses, but its address is not programmed into the control panel’s site-specific
memory. If new devices are detected, the FPD‑7024 shows the following menu (where xxx is
the address of the first new device found):