The second level in your system provides eight options: PROG TIME, SECURITY,
PROG SYSTEM, PROG INPUTS, PROG OUTPUTS, PROG ACCOUNTS, PROG FORMATS, and
HISTORY DEFAULTS. When the D7039 MUX Expander is installed, a ninth option appears:
PROGRAM MUX. The second number in the shortcut enters the Level 2 option and allows
access to Level 3.
Level 3 provides the third set of options that branch from Level 2. The third number in the
shortcut represents the option chosen in Level 3.
For an example of the shortcut to TEST FREQ and TEST TIME, see the following figure. The
sample of the Program Menu Tree shows that to get to TEST TIME and TEST FREQ, you must
go to PROG/0 in Level 1, PROG TIME in Level 2, and AUTO TEST in Level 3. The shortcut is
simply a list of the keys you press to get to the fourth level option. Once you enter the
shortcut, follow the procedural description that appears on the screen of the specific function
you are programming.
Shortcut = 012
LEVEL 1
(Main Menu)
LEVEL 2
LEVEL 3 LEVEL 4
PROG/0
1- PROG TIME
1- SYSTEM
2- AUTO TEST
1- TEST TIME
2- TEST FREQNCY
5
1
2
3
4
6
8
7
Figure 7.4: Example of a programming shortcut
1 Use "0" to select PROG from the Main
Menu which scrolls at the System
Normal display.
5 Password
2 Use "1" to select PROG TIME from
Sub-Level 2.
6 Second number in shortcut
3 Use "2" to select AUTO TEST from Sub-
Level 3. Follow the procedural
description that appears on the
screen.
7 Third number in shortcut
4 First number in shortcut 8 Fourth number in shortcut
Remote programming
The system operates during remote programming so that new alarms end the remote
programming session and report normally. Using the keypads to perform other functions
during remote programming (such as tests and disables) can cause remote programming to
disconnect or other unexpected operations. Avoid downloading programming changes that
cause alarms, because the session disconnects as soon as the alarm occurs, before the
session completes. To indicate that the system is in a special operating mode with user input
7.7
Fire Alarm Control Panels Programming | en 57
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458