Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
PHONE CONTROL #1
1- MONITOR LINE
2- DIALING TYPE
For explanations of the phone control options, see the following sections for Monitor Line and
Dialing Type.
Monitor Line
Shortcut: 0-PROG, 6-PROG ACC’NTS, 2-PHONE CONTROL
The phone line monitor feature, that supervises the connection of the phone line to the
control panel, can be disabled for each phone line. If an IP address is entered for the Phone/
IP number, set the monitor to No. If this is not programmed to No, a trouble is generated.
Choose Line 1 or Line 2 (see the window above). The display scrolls through the Phone
Control options. Press [1] for MONITOR LINE. The following window appears:
MONITOR LINE #1
_______: YES (1) NO (0)
For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
Press [1] for YES or [0/Prog] for NO. The previous window appears.
Dialing Type
Shortcut: 0-PROG, 6-PROG ACC’NTS, 2-PHONE CONTROL
This feature determines the format the control panel uses for dialing on each phone line. The
TONE/PULSE setting first tries tone dialing. If that fails, it switches to pulse dialing. If an IP
address is entered in for the Phone/IP number, the control panel ignores this setting.
Choose Line 1 or Line 2 (see the window below). The display scrolls through the Phone
Control options. Press [2] for DIALING TYPE. The following window appears:
PHONE CONTRO (__)
1- PULSE ONLY
2- TONE/PULSE
3- TONE ONLY
Press the number key that corresponds to your selection. The previous window appears.
Report Steering
Shortcut: 0-PROG, 6-PROG ACC’NTS, 3-RPT STEERING
Different classes of reports can be directed to different phone numbers. Non-supervisory
alarms include fire alarms and waterflow alarms. Supervisory alarms come from points
configured as a supervisory type. Non-supervisory restorals include fire and waterflow
restorals. Supervisory restorals come only from points configured as a supervisory type.
Trouble reports include all point and system troubles and restorals. Tests include Auto Tests,
Manual Tests and Off-normal at Test Reports. The control panel allows the special reports
Silence, Reset, and Drill to be individually directed.
8.6.3
Fire Alarm Control Panels Control Panel Programming | en 83