i
Notice!
This feature offers the use of hexadecimal digits (0 through F). Because the specific keys A
through F are not available on the keypad, use the following equivalent keys: History=A,
Test=B, Disable=C, Drill=D, Silence=E, and Reset=F
NOTICE!
4/2 Zone Report
Shortcut: 0-PROG, 7-PROG FORMATS, 1-4/2 ZONE RPTS
4/2 Zone reports consist of an event type (first digit) and a point number (second digit).
These reports apply only to points, and only when a 3/1 or 4/2 format is selected.
The following window appears:
4/2 ZONE RPT
0- FIRE ALRM D1
1- FIRE RSTR D1
2- WATERFLOW D1
3- SUPERVISE D1
4- TROUBLE D1
5- TRBL RSTR D1
6- DISABLE D1
7- DSBL RSTR D1
8- (RESERVED)
9- MORE
Press the number key that corresponds with your selection of event type (D1 stands for
digit 1). Press [#/Enter].
Pressing [9] retrieves the second digit options (point numbers). The following window
appears:
4/2 ZONE RPT
1- POINT 9 D2
2- POINT 10 D2
3- RETURN TO D1
Press the number key that corresponds to your selection. A window based on your previous
selection allowing entry of hex digits appears:
FIRE ALARM D1 ( )
0 THRU 9
<HISTORY>:A
<TEST>:B
<DISABLE>:C
<DRILL>:D
<SILENCE>:E
<RESET>:F
Enter the digit that corresponds to the selected condition by pressing a number key or one of
the special keys if a hex character is needed. Press [#/Enter] and the previous display
appears.
8.7.1
86 en | Control Panel Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.