4/2 POINT REPORTS
POINT 6 D2: 6
POINT 7 D2: 7
POINT 8 D2: 8
POINT 9 D2: 9
POINT 10 D2: 0
4/2 RPT CODS
SYSTM IN TST: 33
SYS TEST RST: 37
SILENCE: 9F
FIRE DRILL: 33
FIRE DRL RST: 37
OPEN RST RPT: 9F
LOW BATTERY: 69
LOW BATT RST: 79
AC FAILURE: 60
AC FAIL RST: 70
TEST REPORT: 30
OFF NORM TST: 33
PHONE 1 TRBL: 31
PN 1 TRB RST: 35
PHONE 2 TRBL 32
PN 2 TRB RST: 36
SYSTEM TROUB: 33
SYS TRB RST: 37
Multiplex
MUX BUS TYPE:
2 CLASS B
Appendix E: Phone Monitor Troubleshooting
COMM FLT/DATA LOST
A common cause of this fault condition is failing to program Phone/IP Number 2 or Account
Number 2 while some reports are directed to Phone/IP 2 Backup reports are still made to
Phone/IP Number 1. This message warns the installer that Phone/IP Number 2 is not available
if it is needed.
10.5
10.5.1
118 en | Appendices Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.