Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
Each point is individually supervised for proper connection to the common bus (when
over ten points are troubled, up to ten troubles are shown per bus and the balance of the
troubles is indicated by a common bus failure message).
Response time can be set to fast, or programmed from 1 to 89 seconds.
Input points on the SLCs are implemented with a D7042 Eight Input Remote Module.
Enclosure Housing
The standard enclosure is 18 ga., cold-rolled steel, and measures 20.75 in. x 15 in. x 4.25 in.
(52.7 cm x 38.1 cm x 10.8 cm). A keyed lock is included, and the LEDs and LCD display are
visible through the door.
Remote LCD Keypads
Maximum number of keypads: Four FMR‑7033 LCD Fire Keypads.
For wiring Requirements, see Option bus wiring requirements, 34
Remote LED Annunciators
Maximum number of annunciators: Eight D7030 eight-zone LED Annunciators.
For wiring Requirements, see Option bus wiring requirements, 34
D7032 - use with the D7030X
When a D7032 Eight-Zone LED Annunciator Expander is connected to the D7030X, eight
additional LED zones appear. This allows the D7030X/D7032 combination to show 16 LED
zones. Up to eight D7030X/D7032 combinations can be connected to the FPD‑7024 Fire Alarm
Control Panel.
i
Notice!
Each D7030X processes 16 zones of information. If no D7032 is attached, only the lower eight
zones are shown.
i
Notice!
The column labeled “shown on D7030X” in the LED assignments table below applies regard-
less if an attachment of a D7032 to any D7030X is made.
For LED assignments when up to eight D7030X/D7032 combinations are used, see the
following table:
D7030X zones
covered
shown on
D7030X
shown on
D7032 (if
attached)
comments
1 1 to 16 1 to 8 9 to 16 Combination with lowest option
bus address (such as Address 1)
2 17 to 32 17 to 24 25 to 32 Combination with second lowest
option bus address (such as
Address 2)
3 33 to 48 33 to 40 41 to 48 Combination with third lowest
option bus address (such as
Address 3)
2.2.3
2.2.4
2.2.5
2.2.6
10 en | Overview Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.