Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
PROGRAM MUX
1- MUX EDIT
2- MUX PROGRAM
3- BUS TYPE
4- AUTO PROGRAM
From the Program MUX menu, press [1] to select MUX Edit. The following window appears:
DEVICE TYPE ( )
0- NO DEVICE
2- SINGLE INPUT
3- I/O MODULE
4- MUX SMOKE
5- SMOKE W/FRZ
6- DUAL INPUT
7- OCTAL INPUT
Description Model
0- NO DEVICE
2- SINGLE INPUT D7044/M, D7045, FMM-7045, D7052(Class
A)
3- I/O MODULE D7053
4- MUX SMOKE D7050, D7050TH, D343
5- SMOKE W/FRZ Not Used
6- DUAL INPUT D7052(Class B)
7- OCTAL INPUT D7042
Press [0/Prog] for No Device. Then enter the address for the point you wish to delete.
After the device is successfully deleted, you return to the Device Type (MUX Edit) sub-menu.
An unsuccessful deletion results in an error message (see below) followed by the Device Type
(MUX Edit) sub-menu.
ERROR –
DEVICE FAILED
!
Warning!
Dual point removal!
If you remove one point of a dual point address (for example, a D7042 Eight Point Input Mod-
ule), the second point (and subsequent points) at this address are also removed. For exam-
ple, if the first point of a D7042 is removed, the remaining seven points are also removed.
Fire Alarm Control Panels Control Panel Programming | en 97
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458