Figure 4.2: Wiring the D185
1 D185 module 5 Fire control panel
2 To monitoring station bk black
3 D275 bu blue
4 2.2 kΩ EOL ye yellow
The module can signal alarm, trouble, and supervisory conditions. The Wiring the D185 figure,
24 shows the module being used to signal alarm and trouble conditions only. With a third relay
(available from the eight-relay expansion module) and an additional leased line, supervisory
conditions can also be signaled.
In the example in the Wiring the D185 figure, Relay 1 must be programmed to operate on
Alarm (Zone 63) and Relay 2 must be programmed to operate on Trouble (Zone 62). Program
Input 4 to operate as a Supervisory point. Any alarm causes the voltage to the monitoring
station to be interrupted. Placing the D185 in test mode causes a SUPERVISORY TROUBLE.
See also the D185 Installation Manual.
Installing the enclosure
To install the enclosure, follow these instructions:
1. Using the enclosure as a template, mark the top mounting holes on the mounting surface.
2. Start the mounting screws (not supplied) for these two holes.
3. Slide the enclosure onto these screws so that the screws rest on the thinner section of
the holes.
4. Tighten the screws.
4.2
Fire Alarm Control Panels Installation | en 25