If no devices are connected on Bus A, the following window appears. Otherwise an error
message appears.
PROGRAM MUX
1- NORMAL
2- FAST
Select normal programming to add one or two devices. Select fast programming to program
larger quantities of identical devices to sequential addresses.
Normal Programming
If normal programming is selected, the following menu appears allowing selection of the
device type being programmed:
DEVICE TYPE ( )
0- NO DEVICE
2- SINGLE INPUT
3- I/O MODULE
4- MUX SMOKE
5- SMOKE W/FRZ
6- DUAL INPUT
7- OCTAL INPUT
DescriptionModel
0- NO DEVICE
2- SINGLE INPUT D7044/M, D7045, FMM-7045, D7052(Class A)
3- I/O MODULE D7053
4- MUX SMOKE D7050, D7050TH, D343
5- SMOKE W/FRZ Not Used
6- DUAL INPUT D7052(Class B)
7- OCTAL INPUT D7042
Enter the number that corresponds with the device you are adding, or select 0 if you are
removing a device. When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The display asks you to
attach the device being programmed to the terminals for MUX bus A (see the following
window). You can simply hold the device wires on the terminals for the few seconds it takes
to program. The programming operation retries up to three times if the device does not
connect right away.
POINT NUMBER 009
ATTACH DEVICE
Then, the display automatically shows:
POINT NUMBER 009
PROGRAMMING
If the device added is an I/O module, you are asked to enter the four zones to control the relay
output, just as for other relay devices:
OUTPUT ZONE A: _______
(00 - 63): _______
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar
display for Zone B, C and D appears allowing up to four zones to control this output. When all
four zones are assigned, the previous window appears. It confirms the programming operation
and returns to the previous menu.
POINT NUMBER 009
PROGRAMMED
Fire Alarm Control Panels Control Panel Programming | en 91
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458