Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
Timer Programming
Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silence
operation.
Point Programming
For fire points: open = trouble, latching.
Alarm Output Programming
Program notification appliance circuits to activate from the appropriate input points.
Communications Programming
If used for Central Station Service, select a communication format compatible with the
central station. Enable monitoring of both phone lines.
UL Listed Accessory Devices
D132B Multi-use Reversing Relay Module
The D132B is a multi-purpose, fully configurable, smoke power-reversing module for activating
detectors with local annunciation. The D132B operates both two-wire and four-wire circuits
and also works with Class A or Class B initiating circuits. An alarm latch connection is
provided to allow an initiating loop to be held in alarm after the detector loop power is
reversed to activate any sounders. The D132B does not affect compatibility between the FACP
and detectors, or the FACP and Notification Appliance Circuits (NACs).
See also the D132B Installation Guide for detailed installation instructions for the D132B
module. One of the installation options shown in the D132B Installation Guide is also shown in
the following figure:
Fire Alarm Control Panels
Installation | en 23
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458