Press [1] to require a PIN at the local keypad. The following window appears:
LOCAL KEYPD PIN?
_______: YES(1) NO(0)
Press the number key that corresponds to your selection. The existing setting is shown in
front of the colon on the second line. After making your selection, the previous window
appears.
Remote
Shortcut: 0-PROG, 3-PROG SYSTEM, 5-PIN REQUIRED?
The following window appears:
PIN REQUIRED?
1- LOCAL
2- REMOTE
Press [2] to select remote PIN. The following window appears:
REMOTE KYPD PIN?
_______: YES (1) NO (0)
Press the number key that corresponds to your selection and press [#/Enter]. The existing
setting is shown in front of the colon on the second line. After you select the PIN requirement,
the previous window appears.
For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
i
Notice!
A PIN can be required before operations can be performed using the remote keypads on the
option bus. If the remote keypads are not otherwise secured, this option must be set to YES
to comply with NFPA and Local requirements.
NAC silence mode
Shortcut: 0-PROG, 3-PROG SYSTEM, 6-NAC SIL MODE
NAC silence mode allows notification devices to be silenced from the control panel. Any
output configured as silenceable is silenced upon silence operation. You can define audible
only or audible and visible by this option. If silenced, a relay is completely turned off.
The following window appears:
1-AUDIBLE ONLY
2-AUDI & VISI
Press [1] to configure the audible output to be silenceable leaving the visible output to
display. Press [2] to configure both the audible and visible outputs to be silenceable.
8.3.5
66 en | Control Panel Programming Fire Alarm Control Panels