Figure 6.3: Mapping inputs, zones, and outputs
1 Input Point 1 is assigned to Zone 1,
mapped to NAC Point 1.
4 Input Point 4 is assigned to Zone 2,
mapped to NACs 1 and 2.
2 Input Point 2 is assigned to Zone 2,
mapped to NACs 1 and 2.
5 Input Point 5 is assigned to Zone 3,
mapped to NAC 2, LR 1 and RR1.
3 Input Point 3 is assigned to Zone 2,
mapped to NACs 1 and 2.
6 General Alarm Zone 63 drives LR 2.
For pre-assigned zone assignments, see the following table:
Zone Condition
51 Reserved for future use.
52 General Fire Alarm, Waterflow (non-silenceable). Same as Zone 53, but remains
active even while system is silenced.
53 General Fire Alarm (silenceable). Active when a fire alarm condition is present;
does not activate for waterflow.
54 Activates for approximately 7 sec before dialing, to initiate dial tone on a ground
start phone system.
55 General Supervisory (silenceable)
56 General Waterflow (silenceable)
57 Communication Trouble. Active when the dialer fails to communicate; remains
active until communication through the digital communicator is restored.
58 General Supervisory Alarm (non-silenceable). Active when any supervisory alarm
condition is present.
59 Alarm Verification. Active while alarm verification is in progress. This starts with
the first detection of an alarm to be verified and clears in two minutes, or when
system is reset.
60 No AC. Active when AC power fails.