Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
i
Notice!
The @ x shows the address of the relay module in the system. The lower number address is
Relay 1; the higher one is Relay 2.When you address a MUX Module, you assign an address. If
you have a dual point, it would have two consecutive addresses.
Enter the relay you wish to assign and press [#/Enter]. The display shows:
OUTPUT ZONE A:_______
(00-63):_______
Enter the output number (00 to 63) you want to assign to Zone A and press [#/Enter]. A
similar display for Zone B appears. When all four zones are assigned, the previous window
appears.
For pre-assigned zones, see Pre-assigned zone quick reference, 74.
An output point cannot be assigned to more than four zones. Each output does not need to be
assigned to four zones. Each zone can have any number of outputs assigned to it.
Multiplex relays
Shortcut: 0-PROG, 5-PROG OUTPUTS, 2-RELAYS
!
Warning!
Do not use this menu to program addresses configured as inputs.
The display scrolls through the Relay options. Press [4/] for MULTIPLEX. The following
window appears:
MUX OUTPUT
(009 - 255):
Enter the number corresponding with the output to be programmed and press [#/Enter]. The
output number of a multiplex relay is the second point of an I/O module. Adding 1 to the
address of the I/O module gives the address of the relay in the module. When the relay is
selected, the display asks you to enter four zones to activate this output:
OUTPUT ZONE A:_______
(00 - 63):_______
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar
display for Zone B, C and D appears, allowing up to four zones be assigned to this input. When
all four zones are assigned, the previous window appears.
An output point cannot be assigned to more than four zones. Each output does not need to be
assigned to four zones. Each zone can have any number of outputs assigned to it.
PROG ACCOUNTS
PROG ACC’NTS
1- PHONE / IP NUMS
2- PHON CONTROL
3- RPT STEERING
4- RING COUNT
5- COMM. TRIES
6- MACH. BYPASS
8.6
Fire Alarm Control Panels Control Panel Programming | en 77
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458