Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
NAC CONFIG ( )
1- STEADY
2- PULSING
3- CALIFORNIA MARCH
4- TEMPORAL
5- WHEELOCK
6- GENTEX
7- SYSTEM SENSOR
For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
These selections control the pattern (code) for the selected NAC. Press the number key that
corresponds with the desired pattern:
Steady: Output turns on and stays on while the NAC is active.
Pulsing: Output turns on for 0.5 sec and off for 0.5 sec.
California March: Output turns on for 0.25 sec and off for 0.25 sec.
Temporal: Output turns on and off to implement the ANSI standard evacuation pattern
(Temporal code 3).
Wheelock: Output is configured to support Wheelock devices with synchronization
capability, including the ability to silence the horn of a combination horn strobe. The
Wheelock configuration is not supported by remote NACs implemented using a Remote
NAC power supply.
Gentex: Output is configured to support Gentex devices with synchronization capability,
including the ability to silence the horn of a horn strobe combination.
i
Notice!
The Gentex option does not synchronize to the UL864 9th Edition standard.
System Sensor: Output is configured to support System Sensor devices with
synchronization capability, including the ability to silence the horn of a horn strobe
combination.
After you program the desired pattern configuration, the previous window appears.
If you select 3 from the PROG NACs menu, you are asked to enter four zones to activate this
output.
OUTPUT ZONE A (XX)
(00-63):
i
Notice!
XX” indicates the existing setting for each of the four output zone settings.
Enter the desired zone to activate this output and press [#/Enter]. You are asked to enter up
to four zones (A, B, C, D). Enter 00 (or leave it set at “00”) for any unused zones to prevent
unintentional output activation. After all four zones are programmed, the previous window
appears.
For a list of pre-assigned zones, see the following table:
74 en | Control Panel Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.