Enter the description using the numeric, [Silence] and [History] keys, then press [#/Enter] to
save the description.
Point function
Shortcut: 0-PROG, 4-PROG INPUTS, 2-POINT FUNCTION
There are 16 point functions, each of which has programmable features for: configuration
(fire, waterflow, and so on), local only operation, silencing, and loop response.
i
Notice!
At default, points 9 to 255 are programmed as Function 10 which is set as Fire. Function 11 is
set as Supervisory. Function 04 is set as Waterflow 16 second.
The following window appears:
POINT FUNC. (__)
(01 - 16):_______
Enter the function number you wish to program and press [#/Enter]. The following window
appears:
PROG FUNCT
0- CONFIGURE
1- LOCAL ONLY
2- (reserved)
3- SILENCABLE
4- LOOP RESPONS
5- (reserved)
<DRILL> NXT FCT
<HIST> PREV FCT
Enter the function you wish to program.
Configure
Shortcut: 0-PROG, 4-PROG INPUTS, 2-POINT FUNCTION
– Fire: When activated, the point shows FIRE ALARM on control panel and keypads,
activates selected output devices, and sends a Fire Alarm report (if programmed). Fire
points are defaulted to a latch when first configured.
– Waterflow: When activated, the point shows WATERFLOW ALARM on control panel and
keypads, activates selected output devices, and sends a Waterflow Alarm report (if
programmed). Waterflow points are defaulted to a non-verify characteristic when first
configured.
– Supervisory: When activated, the point shows SUPERVISORY ALARM on control panel
and keypads, and sends a Supervisory Alarm report (if programmed). Supervisory points
are defaulted to a non-verify characteristic when first configured.
– Reset: When activated, the point initiates a control panel-reset operation to clear alarms
and reset smoke detectors. Only points 1 to 8 can be configured as reset points.
– Silence: When activated, the point initiates a control panel silence operation to turn off
sounders if the control panel is configured to allow silencing. Only points 1 to 8 can be
configured as silence points.
8.4.2
70 en | Control Panel Programming Fire Alarm Control Panels
2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.