Bosch Appliances FPD-7024 Smoke Alarm User Manual


 
OUTPUT ZONE ZZZ
(01 - 50):_______
Press the number key that corresponds to your selection. ZZZ indicates the point being
programmed. The existing setting is shown on the second line. After you set up the output
zone, the previous window appears.
Verification
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
This feature resets the detector once to determine if the alarm recurs before annunciating or
sending a signal. The total delay introduced by this feature is equal to the smoke power reset
time plus five seconds. Alarm verification cannot be selected for points that are configured as
WATERFLOW or SUPERVISORY types.
Enter the point number you wish to verify and press [#/Enter]. The display scrolls through the
PROG INPUT options.
Press [3] to select VERIFICATION. The following window appears:
ALARM VERIF (ZZZ)
_______: YES(1) NO(0)
ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Press either [1] to verify or [0/Prog] to not verify. The previous window appears.
Latching
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
If a zone is non-latching, the system resets the alarm status automatically (but does not reset
smoke power) when the input restores to the standby condition. Otherwise, the system must
be manually reset.
For acceptable programming selections for UL864 9
th
edition Listed applications, see
Programming features for UL864, 49.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through
the PROG INPUT options.
Press [4/] to select LATCHING. The following window appears:
LATCHING? ZZZ
:YES(1)NO(0)
ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Press the number key that corresponds to your selection. Select YES for alarm.
The previous window appears.
Point description
Shortcut: 0-
PROG, 4-PROG INPUTS, 1-POINT NUMBER
For this feature, use the numeric keys to enter alphanumeric information to identify each input
(such as initiating circuit). The system allows one 16-character description per input. Enter the
point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [5] to select DESCRIPTION. The following window appears:
PNT DSCRPTN ZZZ:
Fire Alarm Control Panels Control Panel Programming | en 69
Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458