Concord Ultra
1
About This
Manual
This manual provides information for planning, installing, programming, and testing this security
system. When necessary, this manual refers you to other documentation included with compati-
ble peripherals.
Planning sheets are included for you to record hardware layout and software programming set-
tings.
About the User’s Guide
The User’s Guide (466-2060) contains user worksheets that should be filled out during the instal-
lation and programming of the system. With two partition systems, a User’s Manual for each par-
tition is suggested.
Special Installation Requirements
This security system can be used as a fire warning system, an intrusion alarm system, an emer-
gency notification system, or any combination of the three.
Some installations may require configurations dictated by city/state codes, insurance, or Under-
writer’s Laboratories (UL). This section describes the various component and configuration list-
ings.
UL Listed Installations
This section describes the requirements for UL Listed installations.
Basic System
• Control Panel (60-960-95)
• Backup Battery 12V 7 AH (60-680)
•SuperBus
®
2000 Fixed Display Touchpad (60-820), 2x16 LCD Touchpad (60-746-01), 2x20
LCD Touchpad (60-803-04), or 2x20 VFD Touchpad (60-804-04)
• Class II 24 VAC, 50 VA Line Carrier Power Transformer (60-779)
• Interior Speaker Siren (60-252), Exterior Speaker Siren (13-060), Slim Line Hardwire Inte-
rior Siren (60-483-01) or Hardwire Exterior Siren (13-046) per partition
Household Burglary Alarm System Unit (UL 1023)
Basic system, plus:
• Hardwire Magnetic Contact (1035-N or 1075-N) or Wireless Learn Mode Door/Window
Sensor (60-362)
• Immediate Beeps set to on
• UL 98 Options set to on
• Receiver Failure set to on (if wireless devices are used)
• Siren Verify set to on
• Exit Delay set to 60 seconds
• Quick Exit set to off
• Siren Timeout set to 4 minutes or more
• Entry Delay set to 45 seconds or less
• RF TX Timeout set to 24 hours (if system includes a built in or SuperBus 2000 RF Receiver
and wireless smoke sensors)
• Extended Delay set to off
• Sleep Time set to off
• Two Trip Error set to off
• Alarm Verify set to off
• Disable Trouble Beeps set to off
Household Fire Warning System (UL 985)
Basic system, plus:
• Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400,
or 2400TH learned into sensor group 26 or Sentrol (ESL) models 429AT, 521B or 521BXT
learned into sensor group 26
• Wireless Smoke Sensor 60-506-319.5, 60-848-02-95 or 60-848-02-95 learned into sensor
group 26