GE 60-960-95 Home Security System User Manual


 
Concord Ultra
41
Low CPU Battery (06004)
Reporting-Global (Default = on)
When this setting is on, the panel reports a low panel battery to the
central station before shutting down.
Note
For UL 1635 listed installations, this feature must be set to on.
¾To turn Low CPU Battery reports off or on:
1. With the display showing LOW CPU BATTERY OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Battery Restoral (06005)
Reporting-Global (Default = off)
If this setting is on, the panel reports to the central monitoring sta-
tion when a wireless sensor or touchpad reports a battery replace-
ment to the panel.
¾
To turn Battery Restoral reports off or on:
1. With the display showing BATTERY RESTORAL OFF/
ON
(current setting), press 1 (off) or 2 (on). The dis-
play flashes the entered setting.
2. Press # and the display shows the new setting.
Buffer Full Rpt (06006)
Reporting-Global (Default = off)
When this setting is on, the panel sends an “event buffer full”
report to the central monitoring station when the event buffer is
nearly full.
¾
To turn Buffer Full Report off or on:
1. With the display showing BUFFER FULL RPT OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Zone Restorals (06007)
Reporting-Global (Default = off)
When this setting is on, the panel reports a restoral to the central
monitoring station for wireless or hardwire zones in alarm before
the alarm is canceled.
Note
As with all GE Security panels, hardwire smoke detectors connected to
Concord Ultra or SnapCard hardwire zones do not send restorals.
¾To turn Zone Restoral reporting off or on:
1. With the display showing ZONE RESTORALS OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.
Two Trip Error (06008)
Reporting-Global (Default = off)
This setting works with the Alarm Verify setting (see “Alarm Ver-
ify” later in this section and Appendix B: Table B1 “Sensor Table
Characteristics”). If Alarm Verify is on, then the panel waits for a
second sensor trip before sending an alarm.
Note
For UL Listed installations, this feature must be set to off.
If Two Trip Error is also on and a second sensor trip does not occur
within a 4-minute time period, then the panel sends an error report
to the central monitoring station.
¾
To turn Two Trip Error off or on:
1. With the display showing TWO TRIP ERROR OFF/ON
(current setting), press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new setting.