Comm Failure (02003)
Phone Options-Global (Default = on)
This setting determines whether the panel activates trouble beeps to alert users on
the premises that communication to the central station failed. Failure notification
occurs after the third unsuccessful reporting attempt to the central station/pager.
If a Phone Supervision Card (60-789) is installed, failure notification can occur
immediately if inadequate phone line voltage is detected upon the initial dialing
attempt.
Note
For UL 1635 listed installations, this feature must be turned on.
¾To turn Communication Failure notifi-
cation off or on:
1. With the display showing COMM FAIL-
URE OFF/ON
(current setting), press 1
(off) or 2 (on). The display flashes the
entered setting.
2. Press # and the display shows the new
setting.
DTMF Dialing (02004)
Phone Options-Global (Default = on)
This setting determines whether the panel uses
DTMF tones (on) or pulse (off) for dialing pro-
grammed phone numbers.
¾
To turn DTMF Dialing off or on:
1. With the display showing DTMF DIALING OFF/ON (current setting),
press 1 (off) or 2 (on). The display flashes the entered setting.
2. Press # and the display shows the new setting.
Dialer Abort (02005)
Phone Options-Global (Default = on)
This setting determines whether or not the user can stop a panel before it sends a
false alarm to the central station.
When this feature is on, alarm reports from sensors in groups 00–20, 34, and 35 can
be aborted. To abort the dialing attempt, the user must enter 1 + user
code within the
Dialer Abort Delay time setting (defaulted to 30 sec). Cancel and restoral reports
from these sensor groups are aborted at the same time. The following reports can
also be aborted.
System Alarm Tamper/Cancel
No Activity Alarm/Cancel
Touchpad Police and Auxiliary Panic/Cancel
Recent Closing and Two Trip Error
Note
Fire alarm reports to the central station cannot be aborted.
¾To turn Dialer Abort off or on:
1. With the display showing DIALER
ABORT OFF/ON
(current setting),
press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the
new setting.
Dialer Abort Delay (02006)
Phone Options-Global (Default = 30 sec.)
This setting determines how much time
the user has to abort a panel report.
Note
For UL Listed systems, the combined time for
the Entry Delay (0310/320) and Dialer Abort
Delay must not exceed 60 seconds.
¾To change the Dial Abort Delay:
1. With the display showing DIAL ABORT DELAY nn SECS (current setting), enter
the desired time (15–45). The display flashes the entered setting.
2. Press # and the display shows the new setting.
Cancel Message (02007)
Phone Options-Global (Default = on)
This setting determines whether or not the
panel displays a cancel message after the
user disarms the system to clear an alarm
condition.
¾
To turn Cancel Message off or on:
1. With the display showing CANCEL MESSAGE OFF/ON (current setting), press
1 (off) or 2 (on). The display flashes the entered setting.
2. Press # and the display shows the new setting.