Carrier 48/50PG C03-14 Air Conditioner User Manual


 
99
APPENDIX A LOCAL DISPLAY AND CCN TABLES (CONT)
MODE OUTPUTS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
STATUS DISPLAY
OUTPUTS UOUTPUT
FANS Fan Outputs
IDF Indoor Fan State On/Off IDFSTATE
F.SPD Commanded Fan Speed xxx FANSPEED
OFC.1 Outdoor Fan 1 Relay On/Off OFC_1
OFC.2 Outdoor Fan 2 Relay On/Off OFC_2
OFC.3 Outdoor Fan 3 Relay On/Off OFC_3
COOL Cool Outputs
CMP.A Circuit A Compressor(s) On/Off COMP_A
CMP.B Compressors B On/Off COMP_B
CMP.C Compressors C On/Off COMP_C
CCH Crankcase Heat Relay On/Off CCH
CRC Cool>Reheat1 Control On/Off CRC
RH2.A Reheat2 Valve A On/Off RH2_A
RH2.B Reheat2 Valve BC On/Off RH2_B
HEAT Heat Outputs
HT.1 Heat Stage 1 Relay On/Off HEAT_1
HT.2 Heat Stage 2 Relay On/Off HEAT_2
ECON Economizer Outputs
EC.CP Econo Commanded Position 0 to 100 % ECONOCMD forcible forcible
EC.AP Econo Actual Position 0 to 100 % ECONOPOS
PE.1 Power Exhaust 1 Relay On/Off PE_1 forcible
PE.2 Power Exhaust 2 Relay On/Off PE_2 forcible
ALRM Alarm Relay On/Off ALMOUT forcible
48/50PG and PM