Carrier 48/50PG C03-14 Air Conditioner User Manual


 
179
Accessory/FIOP Static Pressure Drops (in. wg)* 48/50PM1628
CFM Economizer Humidi-MiZer™ (16, 20, 24) Humidi-MiZer™ (28)
4000 0.02 0.17 -
4500 0.03 0.19 -
5000 0.04 0.21 -
5500 0.05 0.24 -
6000 0.06 0.27 -
6500 0.07 0.31 0.19
7000 0.08 0.35 0.21
7500 0.09 0.39 0.23
8000 0.1 0.43 0.26
8500 0.11 0.48 0.29
9000 0.12 0.52 0.31
9500 0.13 0.57 0.34
10000 0.15 0.62 0.37
10500 0.16 - 0.4
11000 0.17 - 0.43
11500 0.19 - 0.46
12000 0.2 - 0.5
LEGEND
FIOP - Factory-Installed Option
* The static pressure must be added to the external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the
Fan Performance tables to determine blower rpm and watts.
Accessory/FIOP Electric Heat Static Pressure Drop (in. wg) 50PM1628
CFM
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
Nominal Heater
Size (kw)
Pressure Drop (in.
wg)
4800
25
0.01
50
0.02
75
0.03
5000 0.01 0.02 0.04
6000 0.02 0.04 0.06
7000 0.03 0.06 0.08
8000 0.04 0.08 0.12
9000 0.05 0.1 0.15
10000 0.06 0.13 0.2
11500 0.09 0.18 0.27
LEGEND
FIOP - Factory-Installed Option
NOTES:
1. Heaters are rated at 240v, 480v, and 600v.
2. The static pressure must be added to the external static pressure. The
sum and the evaporator entering-air cfm should then be used in
conjunction with the Fan Performance tables to determine blower rpm, bhp,
and watts.
Copyright 2011 Carrier Corp. 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 1/11
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No:48-50PGPM-03T
Replaces: 48-50PGPM-02T
48/50PG and PM