MODE CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
COOL (cont) Cooling Configuration COOL_CFG 15
B2.FN Level 2 Fans B 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
3 (PG0816)
6 (20, PM16)
2 (2428)
HumidiMizer FIOP:
0 (0314)
1 (PG16)
3 (20, PM16)
2 (2428)
CIR_B_2
B3.FN Level 3 Fans B 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
3 (PG0816)
6 (2028, PM16)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (2028, PM16)
CIR_B_3
CIR.C Circuit C 19
CC.LO Circuit C Lockout Temp 0 to 100F °F 0 OATLCMPC
CS.C1 Current Sensing C1 Disable/En
able
Disable (0314,
2028)
Enable (PG16)
C1_SENSE
C1.FN Level 1 Fans C 07 no HumidiMiZer
FIOP:
0 (0314)
1 (PG16)
0 (2028, PM16)
HumidiMiZer FIOP:
0 (PG0316)
1 (2028, PM16)
CIR_C_1
C2.FN Level 2 Fans C 0 to 7 no HumidiMiZer
FIOP:
0 (0314)
3 (PG16)
0 (2028, PM16)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
2 (2028, PM16)
CIR_C_2
C3.FN Level 3 Fans C 0 to 7 no HumidiMiZer
FIOP:
0 (0314)
3 (PG16)
0 (2028, PM16)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (2028, PM16)
CIR_C_3
SST Low Suction Control 39
SST.O Suction OK Temperature 10 to 50 °F 18 SSTOK
SST.1 Low Suction  Level 1 10 to 50 °F 20 SSTLEV1
SST.2 Low Suction  Level 2 5 to 50 °F 15 SSTLEV2
SST.3 Low Suction  Level 3 0 to 50 °F 10 SSTLEV3
CK.DL Delay On Low SST Check 0 to 300 sec 0 SSTCKDLY
OFC Outdoor Fan Control 19
OFC.3 OFC3 Enable. CCH Dis
able
No/Yes No (PG0316)
Yes (2028, PM16)
OFC3_CTL
0.MXP Fan Lev0 Max Pressure 100 to 500 psig 200 LEV0MAXP
1.MXP Fan Lev1 Max Pressure 100 to 500 psig 400 (PG0316)
450 (2028, PM16)
LEV1MAXP
2.MNP Fan Lev2 Min Pressure 100 to 500 psig 150 (PG0316)
200 (2028, PM16)
LEV2MINP
2.ON Fan Lev2 On Temperature 0 to 100 °F no HumidiMiZer
FIOP:
55 (0320)
45 (2428)
HumidiMiZer FIOP:
68 (20, PM16)
61 (2428)(PG0316)
LEV2ON
2.OFF Fan Lev2 Off Temperature 0 to 100 °F no HumidiMiZer
FIOP:
45 (PG0316)
50 (20, PM16)
40 (2428)
HumidiMiZer FIOP:
57 (2028,
PM16)(PG0316)
LEV2OFF
2.MXP Fan Lev2 Max Pressure 100 to 500 psig 400 LEV2MAXP
3.MNP Fan Lev3 Min Pressure 100 to 500 psig 250 LEV3MINP
48/50PG and PM