Carrier 48/50PG C03-14 Air Conditioner User Manual


 
95
APPENDIX A LOCAL DISPLAY AND CCN TABLES (CONT)
MODE RUN STATUS (cont)
ITEM EXPANSION RANGE UNITS CCN TABLE/
SUBTABLE
CCN POINT CCN
WRITE
STATUS
MENU
WRITE
STATUS
HEAT Heating Status HEATDISP
DMD.H Heating Demand xxx.x ^F HEAT_DMD
AVL.H Available Heating Stages x AVLHSTGS
REQ.H Requested Heating Stages x REQHSTGS
MAX.H Max Allowed Heat Stages x MAXHSTGS forcible
LMT.H Max Heat Stage In Effect x HSTGLIMT
IDF Indoor Fan State Off/On IDFSTATE
F.SPD Commanded Fan Speed xxx % FANSPEED
HT.1 Heat Stage 1 Relay Off/On HEAT_1
TG.H1 Heat Stage 1 Timeguard xxx sec TIMGD_H1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
TG.H2 Heat Stage 2 Timeguard xxx sec TIMGD_H2
ECON Economizer Status ECONDISP
EC.CP Econo Commanded Position xxx % ECONOCMD
EC.AP Econo Actual Position xxx % ECONOPOS
EC.MP Min Position in Effect xxx % MIN_POS forcible
IAQ.S IAQ Level (switch) Low/High IAQIN
IAQ IAQ Level (sensor) xxxx IAQ
OAT Outdoor Air Temperature xxx.x °F OA_TEMP
ENTH Outdoor Enthalpy Switch Low/High ENTHALPY
OAQ OAQ Level (sensor) xxxx OAQ
PE.1 Power Exhaust 1 Relay Off/On PE_1
PE.2 Power Exhaust 2 Relay Off/On PE_2
OAU Outside Air Unit Status OAUDISP
OA.RN OAU System Run State 1=AUTO
2=OFF
3=TEST
OAU_RUN
OA.OP OAU Operating Mode 0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
OAU_MODE
UPC UPC Software Version xxxx UPC_VER
OAU OA Unit Software Version xxxx OAU_VER
2P.DM OAU 2position Damper Close/Open OAUDMPR
WHL OAU Wheel Speed xxx % OAUWHEEL
LAT OAU Leaving Air Temp xxx.x °F OAU_LAT
EXAT OAU Exhaust Air Temp xxx.x °F OAU_EXAT
OA.MN Minimum Outside Air CFM xxxxx CFM MINOACFM
DCV.M Min DCV Outside Air CFM xxxxx CFM MINDCVSP
OA.FS OAU OA Fan Speed xxx % OAFANSPD
A.OA Actual Outside Air CFM xxxxx CFM ACTOACFM
C.OA Command Outside Air CFM xxxxx CFM CMDOACFM
PE.OF Power Exhaust CFM Offset xxxxx CFM EXOFFSET
EX.FS OAU Exhaust Fan Speed xxx % OAUPESPD
A.EX Actual Exhaust Air CFM xxxxx CFM ACTEXCFM
C.EX Command Exhaust Air CFM xxxxx CFM CMDEXCFM
BP.SP Building Pressure Setpnt x.xx in H2O OAU_BPSP
BP Building Pressure x.xx in H2O OAU_BP
TM.LO OA Tempring Lockout Temp xx °F OATMPLOC
TM.SP OA Tempring SAT Setpoint xx °F OATMPSPT
OA.HT OAU Tempering Heater xxx % OAHEATER
HRS Component Run Hours STRTHOUR
A1 Compressor A1 Run Hours xxxxx.xx hours HR_A1 forcible
A2 Compressor A2 Run Hours xxxxx.xx hours HR_A2 forcible
B1 Compressor B1 Run Hours xxxxx.xx hours HR_B1 forcible
C1 Compressor C1 Run Hours xxxxx.xx hours HR_C1 forcible
CCH Crankcase Heat Run Hours xxxxx.xx hours HR_CCH forcible
IDF Indoor Fan Run Hours xxxxx.xx hours HR_IDF forcible
OFC.1 Outdoor Fan 1 Run Hours xxxxx.xx hours HR_OFC_1 forcible
OFC.2 Outdoor Fan 2 Run Hours xxxxx.xx hours HR_OFC_2 forcible
OFC.3 Outdoor Fan 3 Run Hours xxxxx.xx hours HR_OFC_3 forcible
HT.1 Heat Stage 1 Run Hours xxxxx.xx hours HR_HTR_1 forcible
HT.2 Heat Stage 2 Run Hours xxxxx.xx hours HR_HTR_2 forcible
PE.1 Power Exhaust1 Run Hours xxxxx.xx hours HR_PE_1 forcible
PE.2 Power Exhaust2 Run Hours xxxxx.xx hours HR_PE_2 forcible
ALRM Alarm Relay Run Hours xxxxx.xx hours HR_ALM forcible
CRC Reheat1 Valve Run Hours xxxxx.xx hours HR_CRC forcible
RH2.A Reheat2 Valve A Run Hrs xxxxx.xx hours HR_RH2_A forcible
RH2.B Reheat2 Valve BC Run Hrs xxxxx.xx hours HR_RH2_B forcible
48/50PG and PM