Carrier 48/50PG C03-14 Air Conditioner User Manual


 
98
APPENDIX A LOCAL DISPLAY AND CCN TABLES (CONT)
MODE SET POINTS
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT
SETPOINT CONFIGURATION
SETPOINTS SET_PNT
OCSP Occupied Cool Setpoint 55 to 80 °F 78 OCSP
UCSP Unoccupied Cool Setpoint 65 to 95 °F 85 UCSP
OHSP Occupied Heat Setpoint 55 to 80 °F 68 OHSP
UHSP Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
GAP HeatCool Setpoint Gap 2 to 10 ^F 5 HCSP_GAP
STO.R SPT Offset Range (+/) 0 to 5 ^F 5 SPTO_RNG
RH.SP Space RH Occupied SP 30 to 100 % 50 SPRH_SP
RH.UN Space RH Unoccupied SP 30 to 100 % 50 SPRH_USP
RH.DB Space RH Deadband 2 to 20 % 8 SPRH_DB
RH.HB Reheat Heat SP Deadband 5 to 5 ^F 2 RH_HSPDB
CA.LO Circuit A Lockout Temp 0 to 100 °F 0 OATLCMPA
CB.LO Circuit B Lockout Temp 0 to 100 °F 0: no HumidiMiZer FIOP
HumidiMiZer FIOP:
40 (PG0816)
0 (2028, PM16)(0307)
OATLCMPB
CC.LO Circuit C Lockout Temp 0 to 100 °F 0 OATLCMPC
HT.LO Heating Lockout Temp 40 to 125 °F 75 OATLHEAT
EH.LO Econo Cool Hi Temp Limit 40 to 100 °F 65 OATLECLH
EL.LO Econo Cool Lo Temp Limit  30 to 50 °F 0 OATLECLL
FC.LO Free Cool Low Temp Limit  30 to 70 °F 50 OATLUEFC
LCSP Low Cool SAT Setpoint 55 to 75 °F 55 (0307)
65 (0828)
LCSASP
HCSP High Cool SAT Setpoint 50 to 70 °F 55 HCSASP
MODE INPUTS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
STATUS DISPLAY
INPUTS UINPUT
STAT Thermostat Inputs
Y1 Thermostat Y1 Input On/Off Y1 forcible
Y2 Thermostat Y2 Input On/Off Y2 forcible
W1 Thermostat W1 Input On/Off W1 forcible
W2 Thermostat W2 Input On/Off W2 forcible
G Thermostat G Input On/Off G forcible
GEN.I General Inputs
FIL.S Filter Status Switch Dirty/Clean FILTSTAT forcible
FAN.S Fan Status Switch On/Off FAN_STAT forcible
FDWN Fire Shutdown Switch On/Off FIREDOWN forcible
ENTH Outdoor Enthalpy Switch High/Low ENTHALPY forcible
RM.OC Remote Occupancy Switch On/Off REM_OCC forcible
HUM Space Humidity Switch High/Low HUM_STAT forcible
CS.IN Current Sensor Inputs
CS.A1 Compressor A1 Feedback On/Off CS_A1
CS.A2 Compressor A2 Feedback On/Off CS_A2
CS.B1 Compressor B1 Feedback On/Off CS_B1
CS.C1 Compressor C1 Feedback On/Off CS_C1
AIR.Q Air Quality Inputs
IAQ.S IAQ Level (switch) High/Low IAQIN forcible forcible
IAQ IAQ Level (sensor) xxxx ppm IAQ forcible forcible
OAQ OAQ Level (sensor) xxxx ppm OAQ forcible forcible
SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible
48/50PG and PM