Fan Performance 48PMD20 Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
 5000
 862 2.65 917 2.93
F
969 3.21
F
1019 3.17
F
1066 3.52
 5500
F
 937 3.26
F
988 3.56 1036 3.53
1083 3.90
G
1127 4.28
 6000  1013 3.58 1060 3.96 1105 4.35
G
1149 4.75
1191 5.16
 6500
 1089 4.48
G
1133 4.89
G
1175 5.31 1216 5.73
H
1256 6.17
 7000 G
 1166 5.52
H
1207 5.96
H
1247 6.41
H
1285 6.86 1323 7.32
 7500
H
 1243 6.71 1282 7.18 1319 7.66 1355 8.14 1391 8.63
 8000
 1320 8.07 1356 8.57 1392 9.08
 8500
1398 9.60
 9000
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
 5000 F
1112 3.88
F
1156 4.25
G
1199 4.63
G
1240 5.02
G
1280 5.42
 5500
G
1171 4.67
G
1212 5.06
1253 5.47
H
1292 5.88
H
1331 6.30
 6000
1232 5.57
H
1271 6.00
H
1310 6.43 1348 6.87 1384 7.31
 6500 H
1295 6.61 1333 7.06 1369 7.52
 7000
1360 7.80 1396 8.27
 7500
 8000
 8500
 9000
LEGEND
Bhp - Brake Horsepower Input to Fan
Boldface indicates field-supplied drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid‐Low Range: 896 to 1227 rpm, 4.26 Bhp (208/230 and 460‐v), 873 to 1108
rpm, 5.75 Bhp (575‐v)
(G) Mid‐High Range: 1113 to 1414 rpm, 5.75 Bhp
(H) High Range: 1096 to 1339 rpm, 8.63 Bhp
All other rpms require field-supplied drive.
2. See General Fan Performance Notes.
48/50PG and PM