Carrier 48/50PG C03-14 Air Conditioner User Manual


 
81
Carrier Accessory Kits
There are specific accessory kits sold for various field installed
accessories. These kits vary based on model, size, voltage,
manufacture date, and duct orientation. Some of these kits include
Economizer, Power Exhaust, and Electric Heat. Refer to the
Controls Quick SetUp section for configuration and more
information on these accessories.
TwoPosition Damper
The two-position outdoor air damper accessory usage depends on
model size and return duct orientation. This accessory wires
directly into the low voltage circuit for the indoor fan control. No
other control configuration is needed.
Indoor Air Quality
The indoor air quality (IAQ) sensor (part no. 33ZCSENCO2) is a
field-installed accessory which measures CO
2
levels in the air.
When installing this sensor, an ECB board must be installed and
the unit must be configured for IAQ use by setting
ConfigurationAIR.QIA.CF to a value of 1, 2, or 3. See the
Indoor Air Quality section for more information.
TB2420mA Input..........
TB3 Sensor Common..........
TBR 24vac Output.........
TBC Common (GND).........
Outdoor Air Quality
The outdoor air quality (OAQ) sensor is a field-installed accessory
that measures CO
2
levels in the air. When installing this sensor, an
ECB board must be installed and the unit must be configured for
OAQ use by setting ConfigurationAIR.QOA.CF to a value
of 1 or 2. See the Indoor Air Quality section for more information.
TB2420mA Input..........
TB3 Sensor Common..........
TBR 24vac Output.........
TBC Common (GND).........
Smoke Detectors
The smoke detectors are field-installed accessories. These detectors
can detect smoke in either the return air (part no.
CRSMKDET003A00) or supply and return air (part no.
CRSMKSUP002A00). When installing either detector, the unit
must be configured for fire shutdown by setting
ConfigurationUNITFS.SW to normally open (1) or normally
closed (2).
TBFire Shutdown1 Dry Contact Source.............
TBFire Shutdown2 Discrete Input to Board...........
TBR 24vac Output.........
TBC Common (GND).........
NOTE: When a Humidi-Mizer system is installed, the inputs to
the fire shutdown are moved to the control harness. See the Third
Party Control section for more information.
Filter Status
The filter status accessory (part no. CRSTATUS002B00) is a
field-installed accessory. This accessory detects plugged filters.
When installing this accessory, the unit must be configured for
filter status by setting ConfigurationUNITFL.SW to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Filter status wires are prerun in the unit harness and located near
the switch installation location. Refer to the Filter Accessory
installation instructions for more information.
Fan Status
The fan status accessory (part no. CRSTATUS003B00) is a
field-installed accessory. This accessory detects when the indoor
fan is blowing air. When installing this accessory, the unit must be
configured for fan status by setting
ConfigurationUNITFN.SW to normally open (1) or
normally closed (2). Normally open (1) is the preferred
configuration.
Fan status wires are prerun in the unit harness and located near the
switch installation location. Refer to the Fan Accessory installation
instructions for more information.
NOTE: The fan status terminals on TB1 are NOT to be used.
Enthalpy Sensors
The enthalpy accessories (part no. CRENTSNG002A00 and
CRENTDIF002A00) are field-installed accessories. The first
accessory (outdoor air only) determines when the enthalpy is low
relative to a fixed reference. Adding the second accessory (return
air) compares the enthalpy between the outdoor and return
airstreams. In each case, the enthalpy 4 to 20 mA signals are
converted to a switch output which is read by the ECB. When
installing this accessory, the unit must be configured for
enthalpy-based control by setting
ConfigurationECONEN.SW to normally open (1). See Fig.
26 and 27 for wiring details.
Normal status is an active switch which tells the control that
enthalpy is LOW. The actual switch terminal LOW is normally
closed. Refer to the Enthalpy Kit installation instructions for more
information on the installation.
Return/Supply Air Temperature Sensor
The temperature sensor (part no. 33ZCSENSAT) is a field-installed
accessory which may be installed on the common return air duct
and/or the common supply air duct near the unit. The duct return
air temperature (RAT) may be selected for display only if the space
temperature offset (SPTO) is not used. When installing the sensor,
the unit must be configured by setting
ConfigurationUNITRAT.S to YES. Using a RAT will allow
differential dry bulb control of the economizer. The duct supply air
temperature (SAT) may be used to replace the SAT sensor that is
internal to the unit. A supply duct SAT measurement is valid for
heating mode display while the factory-standard internal SAT is
not valid for heating due to its location upstream of the heating
section. When installing the supply duct SAT, the unit must be
configured by setting ConfigurationUNITSAT.H to ENBL.
A SAT sensor in the supply duct is the preferred configuration for
systems with Carrier variable volume and temperature (VVT)
accessory controls.
Space Humidistat
The Space Humidistat (part no. −−HL−−38MG029) is a wall
mounted device with an adjustable setpoint to control humidity
levels. The humidistat input is provided on the field connection
terminal board. The Space Humidity Switch configuration,
ConfigurationUNITRH.SW, identifies the normally open or
normally closed status of this input at LOW humidity.
TBHUMIDISTAT1 Discrete Input to Board............
TBHUMIDISTAT2 24 VAC Dry Contact Source.......
NOTE: The humidistat terminals are only in use when the unit is
equipped with the HumidiMiZer factory option.
48/50PG and PM