MODE CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
COOL (cont) Cooling Configuration COOL_CFG
3.ON Fan Lev3 On Temperature 0 to 100 °F no HumidiMiZer FIOP:
65
HumidiMiZer FIOP:
88 (20, PM16)
68 (2428)(PG0316)
LEV3ON
3.OFF Fan Lev3 Off Temperature 0 to 100 °F no HumidiMiZer FIOP:
55
HumidiMiZer FIOP:
78 (20, PM16)
62 (2428)(PG0316)
LEV3OFF
HMZR Humidimizer Config HMZR_CFG 24
REHT Humidimizer Equipped No/Yes No: no HumidiMiZer
FIOP
Yes: HumidiMiZer FIOP
REHEAT 24
R.DEC Reheat2 Stage Decr.
Time
0 to 999 secs 60 RSTAGDEC 28
R.INC Reheat2 Stage Incr. Time 0 to 999 secs 300 RSTAGINC 28
RH.FN Reheat Fan Control No/Yes No (0314)
Yes (1628)
RHFANCTL 28
RF.LV Reheat ODF Fan On
Level
0 to 3 2 (0320)
3 (2428)
RHFANLEV 28
RF. ON Reheat ODF Fan On
Temp
0 to 100 °F 75 (PG0316)
93 (PG2024)(PM1628)
85 (PG 28)
RHFANON 28
RF.OF Reheat ODF Fan Off
Temp
0 to 100 °F 70 (PG0316)
83 (20, PM16)
88 (24)(PM 28)
80 (PG 28)
RHFANOFF 28
RA.LO Reheat2 OAT Limit A 20 to 70 °F 40 OATLRH_A 28
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80 RHSSPL_A 28
RA.HP Reheat2 SSP Hi Limit A 50 to 100 psig 90 RHSSPH_A 28
RB.LO Reheat2 OAT Limit B,C 20 to 70 °F 50 OATLRH_B 28
RB.LP Reheat2 SSP Lo Limit
B,C
50 to 100 psig 80 RHSSPL_B 28
RB.HP Reheat2 SSP Hi Limit B,C 50 to 100 psig 90 RHSSPH_B 28
HEAT Heating Configuration HEAT_CFG 15
HT.TY Type of Heat Installed 0=No Heat
1=Gas
2=Electric
0 (50 series with no elec
tric heat)
1 (48 series)
2 (50 series with electric
heat)
HEATTYPE 21
N.HTR Number of Heat Stages 1 to 2 1 (48 series 1phase, 50
series <15kW)
2 (48 series 3phase, 50
series >=15kW)
NUM_HEAT 22
MRT.H Heat Minimum On Time 60 to 999 sec 120 HMIN_ON 22
MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMIN_OFF 22
H.DEC Heat Stage Decrease
Time
120 to 999 sec 300 HSTAGDEC 21
H.INC Heat Stage Increase
Time
120 to 999 sec 450 HSTAGINC 21
FOD.E Fanoff Delay, Elect Heat 10 to 600 sec 30 ELEC_FOD 17
FOD.G Fanoff Delay, Gas Heat 45 to 600 sec 45 GAS_FOD 17
HT.LO Heating Lockout Temp 40 to 125 °F 75 OATLHEAT 21
SAT 15
SAT.H SAT Heat Mode Sensing Disable/En
able
Disable SAT_HEAT
SAM.L Maximum SAT Lower
Level
85 to 200 °F 140 SATMAX_L
SAM.U Maximum SAT Upper
Level
85 to 200 °F 160 SATMAX_H
SPT Space Temperature 16
HT.PD SPT Heat Demand (+)
Level
0.5 to 5 ^F 1 HDEM_POS
HT.ND SPT Heat Demand ()
Level
5 to 0.5 ^F 1 HDEM_NEG
H.LAG Heat Thermal Lag Factor 0 to 5 1 HEAT_LAG
48/50PG and PM