Carrier 48/50PG C03-14 Air Conditioner User Manual


 
104
APPENDIX A LOCAL DISPLAY AND CCN TABLES (CONT)
MODE CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
ECON Economizer Configuration ECON_CFG 23
EC.EN Economizer Installed No/Yes No: no FIOP
Yes: FIOP
ECONO 23
E.CTL Economizer Control Type 1=Dig/Posi
tion
2=Dig/Com
mand
3=Analog
Ctrl
1 ECON_CTL 14
EC.MN Econo Minimum Position 0 to 100 % 30
0: ERV FIOP
ECONOMIN 23
EC.MX Econo Cool Max Position 0 to 100 % 100 ECONOMAX 23
M.ANG Min Actuator Ctrl Angle 75 to 90 88 MINANGLE 23
EH.LO Econo Cool Hi Temp Limit 40 to 100 °F 65 OATLECLH 23
EL.LO Econo Cool Lo Temp
Limit
30 to 50 °F 0 OATLECLL 23
DF.DB Diff Dry Bulb Control Disable/En
able
Disable DIFFBULB 23
UEFC Unoccupied Free Cooling 0=Disabled
1=Unoc
cpied
2=PreOccu
pancy
2 UEFC_CFG 23
FC.TM Free Cool PreOcc Time 1 to 9999 mins 120 UEFCTIME 23
FC.LO Free Cool Low Temp Limit 30 to 70 °F 50 OATLUEFC 23
PE.EN Power Exhaust Installed No/Yes No: no FIOP
Yes: FIOP
PE_ENABL 24
PE.1 PE Stage1 Econo Position 0 to 100 % 40 PE1_POS 24
PE.2 PE Stage2 Econo Position 0 to 100 % 75 PE2_POS 24
EN.SW Enthalpy Switch 0=No Switch
1=Normal
Open
2=Normal
Closed
0: no FIOP
1: FIOP
ENTHLCFG 10
E.TRV Economizer Travel Time 5 to 300 secs 150 ECONOTRV 104
E.MXB Bottom Stage Max Econo 0 to 100 % 50 ECONMAXB 104
E.MXM Middle Stage Max Econo 0 to 100 % 35 ECONMAXM 104
E.MXT Top Stage Max Econo 0 to 100 % 25 (PG0316)
0 (2028, PM16)
ECONMAXT 104
AIR.Q Air Quality Config. IAQ_CFG 14
IA.CF IAQ Analog Input Config 0=No IAQ
1=DCV
2=Override
IAQ
3=Ctrl Min
Pos
0: no FIOP
1: FIOP
IAQANCFG 14
IA.FN IAQ Analog Fan Config 0=Never
1=Occupied
2=Always
0 IAQANFAN 30
II.CF IAQ Switch Input Config 0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override
N/O
4=Override
N/C
0 IAQINCFG 30
II.FN IAQ Switch Fan Config 0=Never
1=Occupied
2=Always
0 IAQINFAN 34
AQ.MN Econo Min IAQ Position 0 to 100 % 10
0: ERV FIOP
IAQMINP 30
EC.MN Econo Minimum Position 0 to 100 % 30
0: ERV FIOP
ECONOMIN 23
OVR.P IAQ Override Position 0 to 100 % 100 IAQOVPOS 30
OA.CF OAQ Analog Input Config 0=No OAQ
1=DCV
2=Lockout
OAQ
0 OAQANCFG 30
OAQ.L OAQ Lockout Limit 0 to 5000 600 OAQLOCK 30
AQD.L AQ Differential Low 0 to 5000 100 DAQ_LOW 30
AQD.H AQ Differential High 0 to 5000 700 DAQ_HIGH 30
DF.ON Fan On AQ Differential 0 to 5000 600 DAQFNON 34
DF.OF Fan Off AQ Differential 0 to 5000 200 DAQFNOFF 34
I.4M IAQ Sensor Value at 4mA 0 to 5000 0 IAQ_4MA 30
I.20M IAQ Sensor Value at
20mA
0 to 5000 2000 IAQ_20MA 30
O.4M OAQ Sensor Value at
4mA
0 to 5000 0 OAQ_4MA 33
O.20M OAQ Sensor Value at
20mA
0 to 5000 2000 OAQ_20MA 33
H.4M RH Sensor Value at 4mA 0 to 50 % 0 RH_4MA 24
H.20M RH Sensor Value at 20mA 60 to 100 % 100 RH_20MA 24
48/50PG and PM