Carrier 48/50PG C03-14 Air Conditioner User Manual


 
166
Fan Performance 50PM16 Horizontal Supply / Return Units
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
4500 533 1.09 E 603 1.31 E 664 1.53 E 724 1.76 E 784 2.01 E
4800 558 1.25 E 626 1.48 E 685 1.71 E 742 1.95 E 798 2.20 E
5100 584 1.43 E 650 1.68 E 707 1.91 E 761 2.15 E 813 2.40 E
5400 610 1.63 E 674 1.88 E 729 2.13 E 781 2.38 E 831 2.63 E
5700 636 1.85 E 698 2.11 E 753 2.36 E 802 2.62 E 850 2.88 E
6000 663 2.09 E 723 2.35 E 776 2.62 E 825 2.88 E 871 3.14 E
6300 690 2.35 E 748 2.62 E 800 2.89 E 847 3.16 E 892 3.43 E
6600 717 2.62 E 773 2.90 E 824 3.18 E 870 3.46 E 914 3.73 E
6900 744 2.92 E 799 3.20 E 849 3.49 E 894 3.77 E 936 4.06 E
7200 772 3.24 E 825 3.52 E 873 3.82 E 918 4.11 E 959 4.40 F
7500 800 3.58 E 850 3.86 E 898 4.16 E 942 4.47 F 982 4.77 F
CFM
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
4500 845 2.29 E 907 2.59 E 970 2.93 E - - - - - -
4800 854 2.47 E 912 2.76 E 970 3.08 E 1028 3.42 E - - -
5100 866 2.67 E 920 2.96 E 974 3.26 E 1029 3.60 E 1084 3.95 E
5400 881 2.89 E 931 3.18 E 981 3.48 E 1033 3.80 E 1085 4.14 E
5700 898 3.14 E 945 3.42 E 992 3.72 E 1040 4.03 E 1089 4.36 F
6000 916 3.41 E 960 3.69 E 1005 3.98 E 1050 4.29 F 1096 4.61 F
6300 935 3.70 E 978 3.98 E 1021 4.27 F 1063 4.57 F 1106 4.89 F
6600 956 4.01 E 997 4.29 F 1037 4.59 F 1078 4.89 F 1119 5.20 F
6900 977 4.34 F 1017 4.63 F 1056 4.92 F 1095 5.23 F 1133 5.54 F
7200 999 4.69 F 1037 4.99 F 1075 5.28 F 1112 5.59 F 1150 5.90 G
7500 1021 5.07 F 1059 5.37 F 1095 5.67 F 1131 5.98 G 1167 6.29 G
LEGEND
BHP - Brake Horsepower (motor input to fan)
RPM - Revolutions Per Minute (fan speed)
Drive - Motor & Pulley Drive Option Based on 460V motor maximum BHP. See
notes on this page.
NOTES:
Grey Cells - Indicates field-supplied pulley change required.
Do not exceed listed motor maximum BHP value.
Motor Drive Ranges
(E) Low Range:
208/230 and 460V - RPM Range - 685 to 939, Maximum BHP - 4.26
575V - RPM Range - 751 to 954, Maximum BHP - 5.75
(F) Mid-Low Range:
All voltages, RPM Range - 949 to 1206, Maximum BHP - 5.75
(G) Mid-High Range:
All voltages, RPM Range - 941 to 1176, Maximum BHP - 8.63
(H) High Range: Not Used
See General Notes for Fan Performance Data Tables.
Fan Performance 50PM20 Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
5000
575 1.37 642 1.61  700 1.84  754 2.08  808 2.33
5500
619 1.71 682 1.96
 737 2.21  788 2.45  837 2.71
6000
663 2.09 723 2.35
E
 776 2.62
E
 825 2.88
E
 871 3.14
6500
708 2.53 765 2.80  816 3.08  863 3.35  906 3.63
7000 E
753 3.02
E
807 3.30  857 3.59  902 3.88 944 4.17
7500
800 3.58 850 3.86  898 4.16 942 4.47  982 4.77
8000
847 4.20 894 4.48 940 4.80
F
 982 5.11
F
1022 5.43
8500
894 4.88 939 5.17
F
 982 5.49 1024 5.82 1062 6.14
9000 G
941 5.63
G
983 5.92
G
1025 6.24
G
1065 6.58
G
1103 6.92
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
5000
 862 2.60  917 2.89  972 3.20 1028 3.53 1084 3.89
5500
E  886 2.97 E  935 3.25  985 3.55 1035 3.87 1086 4.21
6000
 916 3.41  960 3.69
F
1005 3.98
F
1050 4.29
F
1096 4.61
6500
 949 3.90  990 4.19 1032 4.48 1073 4.78 1114 5.10
7000 F
 984 4.46
F
1023 4.75 1062 5.04 1100 5.34 1139 5.66
7500
1021 5.07 1059 5.37 1095 5.67
G
1131 5.98
G
1167 6.29
8000
1059 5.74 1095 6.05
G
1130 6.36 1165 6.67 1199 6.99
8500
1099 6.47
G
1133 6.79 1167 7.11 1200 7.43
H
1232 7.76
9000 G
1138 7.26 1172 7.59
H
1205 7.93
H
1237 8.26 1268 8.59
LEGEND
Bhp - Brake Horsepower Input to Fan
Boldface indicates field-supplied drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: 685-939 rpm, 4.26 Bhp (208/230 and 460-v), 751-954, 575 Bhp
(575-v)
(F) Mid‐Low Range: 949 to 1206 rpm, 5.75 Bhp
(G) Mid‐High Range: 941 to 1176 rpm, 8.63 Bhp
(H) High Range: 1014 to 1297 rpm, 11.50 Bhp
All other rpms require field-supplied drive.
2. See General Fan Performance Notes.
48/50PG and PM