Carrier 48/50PG C03-14 Air Conditioner User Manual


 
175
Evaporator Fan Motor Specifications 50PM1628 (cont)
UNIT
50PM
DRIVE ORIENTATION VOLTAGE
EFFICIENCY
(%)
MAX BHP MAX AMPS
24
Low Vertical
208 85.8  4.26 10.6
230 85.8  4.26  9.6
460 85.8  4.26  4.8
575 87.5  5.75  6.0
Mid‐Low Vertical
208 87.5  5.37 15.8
230 87.5  5.75 15.4
460 87.5  5.75  7.7
575 87.5  5.75  6.0
Mid‐High Vertical
208 88.5  7.66 22.0
230 88.5  8.51 22.0
460 88.5  8.63 11.6
575 88.5  8.63  9.4
High Vertical
208 89.5  9.94 28.0
230 89.5 10.45 28.0
460 89.5 11.19 15.0
575 89.5 11.50 12.0
Low Horizontal
208 85.8  4.26 10.6
230 85.8  4.26  9.6
460 85.8  4.26  4.8
575 87.5  5.75  6.0
Mid‐Low Horizontal
208 87.5  5.37 15.8
230 87.5  5.75 15.4
460 87.5  5.75  7.7
575 87.5  5.75  6.0
Mid‐High Horizontal
208 88.5  7.66 22.0
230 88.5  8.51 22.0
460 88.5  8.63 11.6
575 88.5  8.63  9.4
High Horizontal
208 89.5  9.94 28.0
230 89.5 10.45 28.0
460 89.5 11.19 15.0
575 89.5 11.50 12.0
28
Low Vertical
208 87.5  5.37 15.8
230 87.5  5.75 15.4
460 87.5  5.75  7.7
575 87.5  5.75  6.0
Mid‐Low Vertical
208 87.5  5.37 15.8
230 87.5  5.75 15.4
460 87.5  5.75  7.7
575 87.5  5.75  6.0
Mid‐High Vertical
208 88.5  7.66 22.0
230 88.5  8.51 22.0
460 88.5  8.63 11.6
575 88.5  8.63  9.4
High Vertical
208 89.5  9.94 28.0
230 89.5 10.45 28.0
460 89.5 11.19 15.0
575 89.5 11.50 12.0
Low Horizontal
208 87.5  5.37 15.8
230 87.5  5.75 15.4
460 87.5  5.75  7.7
575 87.5  5.75  6.0
Mid‐Low Horizontal
208 87.5  5.37 15.8
230 87.5  5.75 15.4
460 87.5  5.75  7.7
575 87.5  5.75  6.0
Mid‐High Horizontal
208 88.5  7.66 22.0
230 88.5  8.51 22.0
460 88.5  8.63 11.6
575 88.5  8.63  9.4
High Horizontal
208 89.5  9.94 28.0
230 89.5 10.45 28.0
460 89.5 11.19 15.0
575 89.5 11.50 12.0
NOTES:
1. Extensive motor and electrical testing ensures that the motors can be utilized with confidence up to the maximum applied bhp, watts, and amps. Using the fan
motor up to the maximum ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
2. Convert bhp to watts using the following formula:
watts =
bhp (746)
motor efficiency
48/50PG and PM