25.4
MAX. TYP.
SPARK GAP
0.120 TO 0.140
[3.05 TO 3.56]
D
D
E-E
SECTION
SCALE 2:1
D-D
SECTION
B-B
SECTION
SCALE 1:1
A-A
SECTION
SCALE 1:1
C-C
SECTION
C
C
SPARK GAP
0.181
[4.6]
C06269
Fig. 70 Spark Gap Adjustment
Filter Drier
Replace whenever refrigerant system is exposed to atmosphere.
Only use factory specified liquid-line filter driers with working
pressures no less than 650 psig. Do not install a suction-line filter
drier in liquid line. A liquid-line filter drier designed for use with
Puron refrigerant is required on every unit.
Protective Devices
Compressor Rotation
Overcurrent
Each compressor has internal line break motor protection.
Overtemperature
Each compressor has an internal protector to protect it against
excessively high discharge gas temperatures.
HighPressure Switch
If the high-pressure switch trips, the compressor will shut down
and the current sensor (3-phase units only) will not detect current.
See the Current Sensor section below for more information.
Current Sensor (CS) (3Phase Units Only)
The purpose of the CS is to detect losses in compressor power.
After detecting a loss in compressor power, unit control locks out
the compressor for 15 minutes. After 15 minutes, the alarm will
automatically reset. If this alarm occurs 3 times consecutively, the
compressor will remain locked out until an alarm reset is initiated
via CCN or manually via the Scrolling Marquee display (see
Alarms and Alerts section for more details).
Evaporator Fan Motor Protection
Indoor-fan motors less than 5 hp are equipped with internal
overcurrent and overtemperature protection. Protection devices
reset automatically. Disconnect and lock out power when servicing
motor. Indoor-fan motors 5 hp and larger are equipped with a
manual reset, calibrated trip, magnetic circuit breaker and
overcurrent protection. Do not bypass connections or increase the
size of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
CondenserFan Motor Protection
Each condenser-fan motor is internally protected against
overtemperature.
Fuses are located in the control box and feed power to the
condenser fan motors. Always replace blown fuses with the
correct size fuse as indicated on the unit fuse label.
Saturated Suction Pressure (SSP)
If the SSP for a particular circuit is reading below the alarm set point
for an extended period of time, that circuit will be shut down. After 15
minutes, the alarm will automatically reset. If this alarm occurs 3 times
consecutively, the circuit will remain locked out until an alarm reset is
initiated via CCN or manually via the Scrolling Marquee display (see
Alarms and Alerts section for more details).
Relief Devices
All units have relief devices to protect against damage from
excessive pressures (i.e., fire). These devices protect the high and
low side and are located at the suction line service port. Protect
joint during brazing operations near joint.
Control Circuit, 24V
Each control circuit is protected against overcurrent by a circuit
breaker. Breaker can be reset. If it trips, determine cause of trouble
before resetting.
Replacement Parts
A complete list of replacement parts may be obtained from any
Carrier distributor upon request.
Diagnostic LEDs
The MBB, ECB, and IGC control boards have LED lights for
diagnostic purposes. The meanings and error codes can be found
in the troubleshooting section of this manual.
EnergyX
For units equipped with the EnergyX factory installed option, there
will be an EnergyXv2 Supplement Installation Instructions in the
units information packet. Refer to this supplement for details on
service and Maintenance.