Carrier 48/50PG C03-14 Air Conditioner User Manual


 
154
Fan Performance 48PMD28 Vertical Supply/Return Units
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
7500 719 2.59 A 770 2.93 A 817 3.26 A 861 3.59 A 903 3.93 B 944 4.28 B
8000 759 3.09 A 808 3.45 A 853 3.81 A 895 4.16 B 935 4.51 B 974 4.87 B
8500 799 3.65 A 846 4.03 A 889 4.41 B 930 4.79 B 969 5.16 B 1006 5.54 B
9000 840 4.28 A 884 4.68 B 926 5.09 B 966 5.48 B 1003 5.88 C 1039 6.28 C
9500 881 4.97 B 923 5.40 B 964 5.83 C 1002 6.25 C 1038 6.67 C 1073 7.09 C
10000 922 5.74 B 963 6.19 C 1001 6.64 C 1038 7.09 C 1074 7.53 C 1108 7.97 C
10500 963 6.59 C 1002 7.06 C 1040 7.54 C 1075 8.01 C 1110 8.47 C 1143 8.93 D
11000 1005 7.52 C 1042 8.01 C 1078 8.51 C 1113 9.01 D 1146 9.50 D 1178 9.98 D
11500 1046 8.53 C 1082 9.05 D 1117 9.57 D 1151 10.09 D 1183 10.60 D 1214 11.11 D
12000 1088 9.64 D 1123 10.18 D 1156 10.72 D 1189 11.26 --- --- --- --- --- --- ---
CFM
Available External Static Pressure (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive
7500 984 4.65 B 1025 5.05 B 1067 5.48 B 1109 5.95 C 1152 6.48 C 1197 7.06 C
8000 1013 5.25 B 1051 5.65 B 1089 6.07 C 1128 6.53 C 1167 7.02 C 1207 7.56 C
8500 1043 5.93 C 1079 6.33 C 1114 6.75 C 1150 7.20 C 1187 7.67 C 1224 8.18 C
9000 1074 6.68 C 1109 7.09 C 1142 7.52 C 1176 7.97 C 1210 8.43 C 1244 8.93 D
9500 1107 7.51 C 1140 7.93 C 1172 8.37 C 1204 8.82 D 1237 9.29 D 1269 9.78 D
10000 1140 8.41 C 1172 8.85 D 1203 9.31 D 1234 9.77 D 1265 10.24 D 1295 10.73 D
10500 1174 9.40 D 1205 9.86 D 1236 10.33 D 1265 10.80 D 1295 11.29 --- --- --- ---
11000 1209 10.46 D 1239 10.95 D 1269 11.43 --- --- --- --- --- --- --- --- --- ---
11500 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
12000 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
LEGEND
Bhp - Brake Horsepower Input to Fan
Rpm - Fan speed
Drive - Drive option code based on 460V motor max BHP
Grey cells indicate field-supplied pulley change required.
Fan Performance 48PME28 and 48PMF28 Vertical Supply/Return Units
CFM
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
7500 743 2.75 A 792 3.09 A 838 3.42 A 881 3.75 B 922 4.09 B 963 4.45 B
8000 785 3.28 A 832 3.64 A 875 3.99 B 916 4.34 B 956 4.70 B 995 5.07 B
8500 827 3.88 A 872 4.26 A 914 4.63 B 953 5.01 B 991 5.38 B 1028 5.77 C
9000 869 4.54 A 912 4.95 B 952 5.35 B 990 5.74 B 1027 6.14 C 1062 6.54 C
9500 912 5.28 B 953 5.71 B 991 6.13 C 1028 6.55 C 1063 6.97 C 1098 7.39 C
10000 954 6.10 C 994 6.55 C 1031 7.00 C 1067 7.44 C 1101 7.88 C 1134 8.32 C
10500 997 7.00 C 1035 7.47 C 1071 7.95 C 1105 8.41 C 1138 8.87 D 1170 9.34 D
11000 1040 7.99 C 1076 8.48 C 1111 8.98 D 1144 9.47 D 1177 9.96 D 1208 10.44 D
11500 1083 9.06 D 1118 9.59 D 1152 10.10 D 1184 10.62 D 1215 11.13 D --- --- ---
12000 1126 10.24 D 1160 10.78 D 1192 11.32 --- --- --- --- --- --- --- --- --- ---
CFM
Available External Static Pressure (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
RPM BHP Driv
e
7500 1003 4.83 B 1045 5.24 B 1086 5.70 B 1129 6.19 C 1173 6.74 C 1218 7.35 C
8000 1033 5.46 B 1071 5.87 C 1109 6.31 C 1148 6.78 C 1188 7.30 C 1229 7.86 C
8500 1064 6.16 C 1100 6.58 C 1136 7.01 C 1172 7.47 C 1208 7.97 C 1246 8.50 C
9000 1097 6.95 C 1131 7.37 C 1165 7.81 C 1198 8.27 C 1233 8.75 D 1267 9.27 D
9500 1131 7.81 C 1163 8.25 C 1196 8.69 D 1228 9.16 D 1260 9.64 D 1292 10.15 D
10000 1166 8.76 D 1197 9.21 D 1228 9.67 D 1259 10.14 D 1289 10.63 D 1319 11.13 D
10500 1201 9.80 D 1232 10.26 D 1261 10.74 D 1291 11.22 --- --- --- --- --- --- ---
11000 1238 10.92 D 1267 11.41 --- --- --- --- --- --- --- --- --- --- --- --- ---
11500 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
12000 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
LEGEND
Bhp - Brake Horsepower Input to Fan
Rpm - Fan speed
Drive - Drive option code based on 460V motor max BHP
Grey cells indicate field-supplied pulley change required.
48/50PG and PM