4.3.2 Analog outputs
The four analog outputs are available on a range of pins, as shown in section 4.2.1.
H Four independent analog outputs.
H Output range: ±10VDC (±0.1%).
H Resolution: 12-bit (accuracy ±4.9mV).
H Output current: 10mA maximum.
H Update frequency: 10kHz maximum (factory default 1kHz).
MintMT and the Mint Motion Library use analog outputs Demand0 and Demand1 to control
servo drives. Demand outputs 0 and 1 correspond to servo axes 4 and 5 respectively. The
Demand2 and Demand3 outputs may be used as general purpose analog outputs. See the
DAC keyword in the MintMT help file.
The analog outputs may be used to drive loads of 1kor greater. Shielded twisted pair cable
should be used. The shield connection should be made at one end only.