Heat & Glo LifeStyle RED60 2159-900 Indoor Fireplace User Manual


 
Heat & Glo • RED60 • 2159-900 Rev. R • 9/1288
A. IntelliFirePlus™IgnitionSystem(continued)
4. (Continued) Pilot
lights but contin-
ues to spark, and
main burner will not
ignite. (If the pilot
continues to spark
after the pilot ame
has been lit, ame
rectication has not
occurred.)
C. Module is not grounded. Verify module is securely grounded to metal chassis of appliance.
Verify that wire harness is rmly connected to the module.
D. Damaged pilot assembly or con-
taminated ame sensing rod.
Verify that ceramic insulator around the ame sensing rod is not
cracked, damaged, or loose. Verify connection from ame sensing
rod to white sensor wire. Polish ame sensing rod with ne steel
wool to remove any contaminants that may have accumulated on
ame sensing rod. Verify continuity with a multi-meter with ohms set
at lowest range. Replace pilot if any damage is detected.
B. PVI-DVPTroubleshooting
Symptoms
PossibleCauses CorrectiveAction
IntelliFirePlusSystem
Main Closes/ Pilot open, 5 seconds later
pilot sparking with Blower ON. If condition
persists for 60 seconds, 8K-1 locks out with
3 LED alarm.
Pilot Rectication Failure 1. Verify that black wire on IPI wire harness is
properly grounded to the replace chassis.
2. Verify that pilot is not being compromised
by draft such that it fails to rectify. With the
glass assembly in place, verify that the pilot
ame is engulng the ame sensing rod on
the left side of the pilot hood. With a multi-
meter, verify that the current in series be-
tween the module and the sense lead is at
least 0.14 microamps.
3. Verify that line inlet pressure is within range
on rating plate and correct pilot orice is in
pilot.
4. If #1-4 are correct, replace IPI module.
Pilot and Main shut down and 8K1-PVI
locks out with 4 LED alarm.
Blocked Flue/Insufcient Draft 1. Verify the teon pressure tube is connected
between blower impeller housing and vacu-
um switch.
2. Verify that wiring within PVI is correct and
that the blower operates during the ignition
command.
3. Verify that the venting is connected and
sealed properly.
4. Verify that the vent termination is not blocked.
5. If #1 thru #4 are complete, connect black and
red wires to bypass vacuum switch. If mal-
function is corrected, lock-out system until
the vacuum switch can be replaced.
Main Closes, 5 seconds later pilot spark-
ing with Blower ON. If condition persists
for 60 seconds, 8K-1 locks out with 3 LED
alarm.
Shorted Pilot Sense 1. Verify that the white sensor lead is properly
connected to the S-terminal on the module.
2. Check for soot deposits on the pilot sense
rod, adjacent shielding, or logs. If so, clean af-
fected parts.
3. Verify that the white sense lead from the pi-
lot is not damaged or melted within the rebox
or valve compartment. Replace pilot if damage
exists.
Main Closes, 5 seconds later pilot spark-
ing with Blower ON. If condition persists
for 60 seconds, 8K-1 locks out with 3 LED
alarm.
Disconnected Pilot Sense Verify that white sensor lead is properly con-
nected to the S-terminal and the orange ignitor
lead is connected to the I-terminal on the mod-
ule
If given ignition command in both ON and
REMOTE modes, system immediately
locks-out with 3 LED alarm. Does not
spark or attempt to ignite.
Pre-Existing/False Pilot Flame Check for pre-existing pilot ame. If so, the
valve is defective and should replaced.