Heat & Glo LifeStyle RED60 2159-900 Indoor Fireplace User Manual


 
Heat & Glo • RED60 • 2159-900 Rev. R • 9/1234
Figure7.26
H
1
V
2
V
1
TopVent-VerticalTermination
Ventingwith2elbows
Note: Use DVP Series
components only.
V
1
Minimum V
1
+ V
2
+ H
Maximum
2 ft. 610 mm 50 ft. 15.2 m
3 ft. 914 mm 60 ft. 18.3 m
4 ft. 1219 mm 70 ft. 21.3 m
V
1
+ V
2
+ H
1
= 70 ft. (21.3 m) Maximum
Note: PVI-DVP can be located in any
position except V
1
.
WARNING! Risk of re and burns!
DO NOT install PVI-DVP with the
access panel facing upward. Over-
heating may occur.
Note: Must have 24 inches minimum
vertical vent prior to attaching any
elbow to the appliance.