NAILING TABS
BOTH SIDES
Figure5.3NailingTabLocations
D. MantelandWallProjections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specied. Framing or nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
CombustibleMantels
Figure5.4 MinimumVerticalandMaximumHorizontal
DimensionsofCombustibles
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
7
8
9
10
11
12
13
43
TO CEILING
9
10
11
12
8
7
6
25
18
Note: All
measurements
in inches.
Note: For non-combustible replace nish material (marble,
stone, etc) specications refer to Section 13.
Non-CombustibleMantels
Figure5.5MinimumVerticalandMaximumHorizontal
DimensionsofNon-Combustibles
MEASUREMENTS FROM TOP EDGE OF THE
FIRESCREEN DOOR ASSEMBLY
8
9
10
16
7
6
5
4
1
2
3
4
5
6
12
43
MAX.
MIN.
TO CEILING
1/2
Note: All
measurements
in inches.
Figure5.6 MantelLegorWallProjections
(Acceptableonbothsidesofopening)
Mantel Legs Or Wall Projections Extending
PastTheFaceOfTheFireplace
UNLIMITED
6 IN. MIN.
2 IN.
MIN.
FIREPLACE
OPENING
TOP VIEW
4 IN.
MAX.
= ACCEPTABLE
NON-COMBUSTIBLE
MANTEL LEG
ZONE