Carrier 48AY020-060 Air Conditioner User Manual


 
9
Fig. 7 — Base Unit Dimensions — 48AJ,AK060
NOTES:
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue dis-
charge facing economizer inlet.
Min Clearances to be:
Adjacent Units: 15-0 [4572].
Top of Units: No Overhang.
Condenser Coil: 4-0 [1219].
Economizer Side: 6-0 [1829].
Heat Side: 4-0 [1219].
Filter Access Side: 15-0 [4572]. (For
removal of evaporator coil.)
4. For smaller service and operational clear-
ances contact Carrier Application Engineer-
ing Department.
BASE UNIT WEIGHTS
(See Note 6) lbs (kg)
060
48AJD/AKD 8930 (4051)
48AJE 9170 (4159)
UNIT SIZE
CENTER OF GRAVITY
% OF TOTAL WEIGHT
AT EACH CORNER
ft-in. Millimeters
A B AB1234
48AJD/AKD060 10-7
11
/
16
3-10
19
/
32
3242 1184 21.7 19.3 27.7 31.2
48AJE060 11-2
11
/
16
4-
19
/
32
3422 1235 23.9 19.4 25.4 31.3
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted
on dunnage, it is recommended the ducts must be supported by cross braces as
done on accessory roof curb.
6. Base unit weights include outdoor air hoods and filters (indoor fan motor is not
included). Add indoor motor, FIOPs and accessories for total operating weight.
7. VAV motor weights include indoor motor, VFD, compressor electric unloaders,
VFD transducer and associated wiring.
8. Dimensions are in inches [mm].