Table 35 — User Defined Set Points
LEGEND
Table 36 — Software Control Link Points
LEGEND
SET POINT
NAME
FORMAT DESCRIPTION LIMITS DEFAULT
OHSP xx.xF Occupied Heat Set Point 55 to 80 F 68 F
OCSP xx.xF Occupied Cool Set Point 55 to 80 F 78 F
UHSP xx.xF Unoccupied Heat Set Point 35 to 80 F 55 F
UCSP xx.xF Unoccupied Cool Set Point 75 to 110 F 90 F
SASP xx.xF Supply Air Set Point 45 to 70 F 55 F
OATL xx.xF Hi OAT Lockout Temperature 55 to 75 F 65 F
NTLO xx.xF Unoccupied OAT Lockout Temperature 40 to 70 F 50 F
RTIO xx.x Reset Ratio 0 to 10 3
LIMT xx.xF Reset Limit 0 to 20° F 10° F
MDP xxx% Minimum Damper Position 0 to 100% 20%
LOWMDP xxx%
Low Temperature Minimum
Damper Position Override
0 to 100% 100%
IAQS xxxx IAQ Set Point 1 to 5000 PPM 650 PPM
UHDB xx.xF Unoccupied Heating Deadband 0 to 10° F 1° F
UCDB xx.xF Unoccupied Cooling Deadband 0 to 10° F 1° F
LTMP xxx% Low Temp. Min. Position 0 to 100% 10%
HTMP xxx% High Temp. Min. Position 0 to 100% 35%
PES1 xxx% CV Power Exhaust Stage 1 Point 0 to 100% 25%
PES2 xxx% CV Power Exhaust Stage 2 Point 0 to 100% 75%
CV Constant Volume
IAQ Indoor Air Quality
OAT Outdoor-Air Temperature
SET POINT DESCRIPTION SET POINT DESCRIPTION
CV Data
SPT Space Temperature HS2 Heat Stage 2
SAT Supply-Air Temperature STO Space Temp. Offset
RAT Return-Air Temperature CVPE1 CV Power Exhaust Stg 1
OAT Outside-Air Temperature CVPE2 CV Power Exhaust Stg 2
CLSP Control Set Point VAV Data
CCAP Cooling % Total Capacity HIR Heat Interlock Relay
HCAP Heating % Total Capacity SPTRESET Space Temp. Reset
ECOS Economizer Active CMP1 Compressor 1
SFSTAT Supply Fan Status CMP1SAFE Compressor 1 Safety
SF Fan Relay CMP2 Compressor 2
ECONPOS Economizer Position CMP2SAFE Compressor 2 Safety
IQMP Min. Damper Position ULD1 Unloader 1
PEXE Power Exhaust Enable ULD2 Unloader 2
FLTS Filter Status OFC1 Outdoor Fan 1
FAS Field Applied Status OFC2 Outdoor Fan 2
RMTOCC Remote Occupied Mode Y1 Y1 — Call for Cool 1
General Data Y2 Y2 — Call for Cool 2
HS1 Heat Stage 1 W1 W1 — Call for Heat 1
ENTH Enthalpy W2 W2 — Call for Heat 2
IAQI Indoor Air Quality G G — Call for Fan
IAQO Outdoor Air Quality CDEVCODE CONQUEST DEVICE CODE
SATRES SAT Reset CDEVURST CONQUEST UNIT RESET
ALMLIGHT Alarm Warning Light CDEVBCAK CONQUEST BROADCAST ACK
DL Demand Limit Switch PE1 Mod. Power Exhaust Stg 1
EVAC Evacuation PE2 Mod. Power Exhaust Stg 2
PRES Pressurization PE3 Mod. Power Exhaust Stg 3
PURG Smoke Purge PE4 Mod. Power Exhaust Stg 4
FSD Fire Shutdown PE5 Mod. Power Exhaust Stg 5
PE6 Mod. Power Exhaust Stg 6
CV Constant Volume
VAV Variable Air Volume