Carrier 48AY020-060 Air Conditioner User Manual


 
31
Features with Thermostat Control of Unit
two-stage heating
two-stage cooling
control of unit using Y1, Y2, W1, W2, and G thermostat
inputs
control of the indoor fan
outdoor-air temperature/supply-air temperature
monitoring
control of an outdoor air condenser fan based on out-
door-air temperature
control of modulating economizer damper to provide
free cooling when outdoor conditions are suitable, using
supply-air temperature as a control point
control of the economizer damper and indoor fan to
obtain unoccupied free cooling
provide power exhaust output to an external power
exhaust controller
support a field test for field checkout
control of 2 stages of CV power exhaust
compressor Time Guard® (power up, minimum off and
on times)
compressor lockout during low supply-air temperature
Additional features are provided by accessing the standard
unit control board via software with a computer. These features
are:
electronic expansion board features (if installed)
control board diagnostics
ability to change supply air set point (economizer control)
ability to change high outdoor temperature lockout set
point (economizer control)
ability to change power exhaust set points
NOTE: A CV unit without a thermostat requires a field-
supplied sensor for operation.
Features with Sensor Control of Unit (Stand-Alone Applica-
tions — Unit control is limited to CV unoccupied default set
points, 90 F for cooling, 55 F for heating unless a computer has
been used to change the set points. There are 2 sensor options
available:
T-55 sensor will monitor room temperature and provide
unoccupied override capability (1 hour)
T-56 sensor will monitor room temperature, provide
unoccupied override capability (1 hour), and provide a
temperature offset of 5° F.
Standard features are:
support of remote occupied/unoccupied input to start and
stop the unit
cooling capacity control of 3 stages using economizer
and 2 compressors to maintain space temperature to an
occupied or unoccupied set point
enable heating or cooling during unoccupied periods as
required to maintain space temperature within the unoc-
cupied set points
adjustment of space temperature set points of ±5° F when
using a T-56 sensor
provides CCN (Carrier Comfort Network) IAQ (Indoor-
Air Quality) participation
control of modulating economizer damper to maintain
indoor air quality (IAQ) when outdoor conditions are
suitable (this function is provided in the base unit con-
trols on units with serial number 0600F or later)
NOTE: The IAQ sensor must be set for current output (4 to
20 mA), not voltage output. Ensure the jumper on the sensor is
in the upper position. See Fig. 25.
Additional features with sensor control of unit (with com-
puter access or Remote Enhanced Display) are:
365-day timeclock with backup (supports minute, hour,
day of week, date, month, and year)
daylight savings time function
occupancy control with 8 periods for unit operation
holiday table containing up to 18 holiday schedules
ability to initiate timed override from T-55 or T-56 sen-
sors for a timed period of 1 to 4 hours
ability to use multiple space temperature sensors to aver-
age the space temperature
supply-air temperature reset for the supply-air tempera-
ture set point
temperature compensated start to calculate early start
times before occupancy
access to the Display, Maintenance, Configuration, Ser-
vice, and Set Point data tables through network software
loadshed and demand limiting
When the unit is equipped with a field-supplied space tem-
perature sensor and a remote contact closure (remote start/
stop) on the base control board, the occupied default set points
will monitor unit operation. The occupied default set points are
78 F cooling and 68 F heating (if heating is present). See
Fig. 26 for remote start/stop wiring.
NOTE: For units with a field-supplied space temperature sen-
sor which have not had the base unit control board accessed
via software to set an occupancy schedule, the remote start/
stop closure will allow the unit to operate in the pre-configured
occupied default set points of 78 F cooling and 68 F heating.
Without this feature, the unit will control to the unoccupied
default set points of 90 F cooling and 55 F heating.
Fig. 24 — Supply-Air Thermistor Connections