Carrier 48AY020-060 Air Conditioner User Manual


 
35
Table 7 — Electrical Data — 48AJ,AK,AW,AY Units
LEGEND
*Fuse or HACR circuit breaker per NEC.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
% Voltage imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
UNIT SIZE
48AJ,AK,
AW,AY
NOMINAL
VOLTAGE
(3 PH, 60 Hz)
VOLTAGE RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
POWER
SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty FLA Hp FLA
FLA
(total)
MCA MOCP*
020
208/230 187 253 39.1 228 25.6 160 2
5.3
(ea)
5 16.7/15.2
101.8/100.3 125/125
23.6/23.6 125.4/123.9 150/150
10 30.8/28.0
115.9/113.1 150/150
23.6/23.6 139.5/136.7 175/175
15 46.2/42.0
133.1/127.8 175/150
23.6/23.6 156.7/151.4 200/175
460 414 508 19.9 114 11.5 80 2
2.7
(ea)
57.6
—49.460
12.6 62.0 80
10 14
—55.870
12.6 68.4 80
15 21
—63.180
12.6 75.7 90
575 518 632 16 91 9.6 64 2
2.4
(ea)
56.1
—40.550
12.6 53.1 60
10 11
—45.460
12.6 58.0 70
15 17
—51.760
12.6 64.3 80
025
208/230 187 253 39.1 228 39.1 256 2
5.3
(ea)
7.5 24.2/22.0
122.8/120.6 150/150
23.6/23.6 146.4/144.2 175/175
10 30.8/28.0
129.4/126.6 150/150
23.6/23.6 153.0/150.2 175/175
15 46.2/42.0
146.6/141.3 175/175
23.6/23.6 170.2/164.9 200/200
460 414 508 19.9 114 19.9 114 2
2.7
(ea)
7.5 11
—61.280
12.6 73.8 90
10 14
—64.280
12.6 76.8 90
15 21
—71.590
12.6 84.1 100
575 518 632 16 91 16 91 2
2.4
(ea)
7.5 9
—49.860
12.6 62.4 70
10 11
—51.860
12.6 64.4 80
15 17
—58.170
12.6 70.7 80
FLA Full Load Amps
HACR— Heating, Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
7
457