Fig. 6 — Base Unit Dimensions — 48AJ,AK035-050
NOTES:
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer
inlet.
Min Clearances to be:
Adjacent Units: 15-0 [4572].
Top of Units: No Overhang.
Condenser Coil: 4-0 [1219].
Economizer Side: 6-0 [1829].
Heat Side: 4-0 [1219].
Filter Access Side: 10-0 [3048]. (For removal of evaporator coil.)
4. For smaller service and operational clearances contact Carrier Appli-
cation Engineering Department.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is
mounted on dunnage, it is recommended the ducts must be supported
by cross braces as done on accessory roof curb.
6. Dimensions are in inches [mm].
UNIT SIZE
OPERATING
WEIGHT*
(lbs)
A
(ft-in.)
B
(ft-in.)
CORNER WEIGHT (lbs)
1234
48AJ/AK (Low Heat) 035 6004 7-8
11
/
16
3-10
7
/
8
1380 1209 1595 1820
48AJ (High Heat) 035 6164 7-10
1
/
8
3-11
3
/
16
1447 1251 1607 1859
48AJ/AK (Low Heat) 040 6514 7-5
5
/
16
3-10
7
/
8
1442 1264 1779 2030
48AJ (High Heat) 040 6674 7-6
13
/
16
3-11
3
/
16
1512 1307 1787 2068
48AJ/AK (Low Heat) 050 6725 7-3
11
/
16
3-10
1
/
2
1449 1294 1878 2104
48AJ (High Heat) 050 6885 7-5
3
/
16
3-10
13
/
16
1519 1337 1886 2142
UNIT SIZE
OPERATING
WEIGHT*
(kg)
A (mm) B (mm)
CORNER WEIGHT (kg)
1234
48AJ/AK (Low Heat) 035 2723 2355 1191 626 548 723 826
48AJ (High Heat) 035 2796 2390 1199 656 567 729 843
48AJ/AK (Low Heat) 040 2955 2268 1191 654 573 807 921
48AJ (High Heat) 040 3027 2306 1199 686 593 811 938
48AJ/AK (Low Heat) 050 3050 2228 1181 657 587 852 954
48AJ (High Heat) 050 3123 2266 1189 689 607 856 972