Carrier 48AY020-060 Air Conditioner User Manual


 
11
Fig. 9 — Base Unit Dimensions — 48AW,AY035-050
NOTES:
1. Weights include economizer (standard).
2. Center of Gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet.
Min Clearances to be:
Adjacent Units: 15-0 [4572].
Top of Units: No Overhang.
Condenser Coil: 4-0 [1219].
Economizer Side: 6-0 [1829].
Heat Side: 4-0 [1219].
Filter Access Side: 10-0 [3048]. (For removal of evaporator coil.)
4. For smaller service and operational clearances contact Carrier Application Engineering Department.
5. Dimensions are in inches [mm].
UNIT SIZE
OPERATING
WEIGHT*
(lbs)
A
(ft-in.)
B
(ft-in.)
CORNER WEIGHT (lbs)
1234
48AW/AY (Low Heat) 035 6044 7- 8
11
/
16
3-10
7
/
8
1389 1217 1606 1832
48AW (High Heat) 035 6204 7-10
1
/
8
3-11
3
/
16
1456 1259 1617 1871
48AW/AY (Low Heat) 040 6554 7- 3
11
/
16
3-10
7
/
8
1451 1271 1790 2042
48AW (High Heat) 040 6714 7- 6
13
/
16
3-11
3
/
16
1521 1315 1798 2080
48AW/AY (Low Heat) 050 6765 7- 3
11
/
16
3-10
1
/
2
1458 1301 1889 2117
48AW (High Heat) 050 6925 7- 5
3
/
16
3-10
13
/
16
1528 1345 1897 2155
UNIT SIZE
OPERATING
WEIGHT*
(kg)
A (mm) B (mm)
CORNER WEIGHT (kg)
1234
48AW/AY (Low Heat) 035 2741 2355 1191 630 552 728 831
48AW (High Heat) 035 2814 2390 1199 661 571 734 849
48AW/AY (Low Heat) 040 2973 2268 1191 658 577 812 926
48AW (High Heat) 040 3045 2306 1199 690 596 816 944
48AW/AY (Low Heat) 050 3069 2228 1181 661 590 857 960
48AW (High Heat) 050 3141 2266 1189 693 610 860 977