Mitsubishi Electronics QJ71DN91 Water System User Manual


 
3 - 49 3 - 49
MELSEC-Q
3 SPECIFICATIONS
(31) Slave Function Receive Data (addresses 0B00
H
to 0B3F
H
/2816 to
2879)
The data received from the master node is stored. The data of the size that is set
by the "setting area of the number of slave function reception bytes" becomes
valid.
0B00
H
0B01
H
0B02
H
2nd byte 1st byte
3rd byte
4th byte
6th byte
5th byte
(32) Slave Function Transmit Data (addresses 0C00
H
to 0B3F
H
/3072 to
3135)
The data to be transmitted to the master node is written by the TO instruction.
The I/O data of the size, which is set by the "setting area of the number of slave
function transmission bytes," is sent.
0C00
H
0C01
H
0C02
H
2nd byte 1st byte
3rd byte
4th byte
6th byte
5th byte
POINT
When the QJ71DN91 is used as the master node, set an even number of byte
modules. If an odd number of byte modules is set and word modules and double-
word modules are set at the same time, the word data and double-word data