Mitsubishi Electronics QJ71DN91 Water System User Manual


 
App - 3 App - 3
MELSEC-Q
APPENDIX
Appendix 3 Parameter Setting Sheet (For the Master Function)
Item Setting range
Buffer memory
address
Remark Setting value
Constant scan 0 ms to 65535 ms 01D7
H
Setting to make the link scan time constant.
Item Setting range
Buffer memory
address
Remark Setting value
Higher byte: 01
H
to
04
H
or 80
H
Node that supports 01
H
UCMM and uses either message group 3, 2 or 1.
Node that supports 02
H
UCMM and uses message group 2.
Node that supports 03
H
UCMM and uses message group 1.
Node that does not support 04
H
UCMM (group 2 dedicated server).
80
H
Reserved node
Node number
and message
group of the
nth slave node
Lower byte:
00h to 3F
H
(0 to 63)
01D8
H
+( -1) 8
Node number of the nth slave node
Connection
type of the nth
slave node
0001
H
, 0002
H
,
0004
H
, 0008
H
,
01D9
H
+( -1) 8
Connection type of I/O communication
0001
H
: Polling
0002
H
: Bit strobe
0004
H
: Change-of-state
0008
H
: Cyclic
Higher byte:
Output byte module
count
Byte module
count of the
nth slave node
Lower byte:
Input byte module
count
01DA
H
+( -1) 8 Both are in byte unit.
Higher byte:
Output word module
count
Word module
count of the
nth slave node
Lower byte:
Input word module
count
01DB
H
+( -1) 8 Both are in word unit.
Higher byte:
Output double-word
module count
Double-word
module count
of the nth
slave node
Lower byte:
Input double-word
module count
01DC
H
+( -1) 8 Both are in double-word unit.
Expected
packet rate of
the nth slave
node
Communication
watchdog timer value
for slave node (ms)
01DD
H
+( -1) 8
Set the communication watchdog timer value for a slave node. When
communication between the master node and the first slave node is
interrupted for the period of time set here, the first slave node performs the
operation specified in buffer memory 01DE
H
.
Setting value = 0000
H
(default value) 500 ms
Setting value
0000
H
Setting value -1 is the expected packet rate (ms).
Watchdog
timeout action
of the nth
slave node
0000
H
, 0001
H
0002
H
, 0003
H
01DE
H
+( -1) 8
Watchdog timeout action at a slave node
Setting value = 0000
H
: Timeout (default value)
Setting value = 0001
H
: Timeout
Setting value = 0002
H
: Auto delete
Setting value = 0003
H
: Auto reset
Production
inhibit time of
the nth slave
node
Minimum
transmission interval
of slave node (ms)
01DF
H
+( -1) 8
Minimum transmission interval of a slave node: Set the minimum time that is
required for the slave node to prepare transmission data.
The master node sends the polling request and bit strobe request to the slave
node using this time interval.
Setting value = 0000
H
: (default value) 10 ms
Setting value
0000
H
: Setting value -1 is the minimum transmission
interval (ms).
Note: (1) "n" indicates a number between 1 and b3.