Zone List Programming After entering all relay menu items, up to four (4) zone lists can be entered by
entering 00 at the ENTERÊRELAYÊNo. prompt.
Enter Zone LIST
00=QUIT 00
Enter the zone list number 1-4.
01 Enter Zn Num.
00=QUIT 00
Enter each zone to be included in this zone list,
pressing [*] to enter each zone number.
01 Del Zn LIST?
Enter 0 to save the zone list entered. Enter 1 to
delete that zone list.
01 Delete Zone?
0=NO 1=YES
Enter 1 to delete one or more zones in that zone list.
Enter 0 if no changes are necessary. If 1 is entered,
the following screen will appear, otherwise the zone
list no. prompt will reappear.
01 Zn to Delete?
00=QUIT 00
Enter each zone number to be deleted from the
zone list, pressing [*] after each number.
View Zn LIST
00=QUIT 00
This will appear if 00 is pressed at the ENTER ZONE
LIST prompt. Enter the zone list number that you
wish to view.
XX ASSIGNED ZONE
00=QUIT 00
Press [*] to scroll through all zones in that list. Enter
00 to quit.
Programming Relays for
Silencing of External
Sounders When Using the
VIM
The system can be programmed to silence external sounders during a 2-way
voice session (VIM active) by using two relays connected in series. An example
shows relays 1 and 2 of the Relay Module connected as shown in the diagram
below. Program the relay that controls the bell/siren (#1) as usual and the other
relay (#2) as shown below. This programming enables the sounders when the
VIM is not active and disables the sounders when the VIM is active.
Ex. Relay #2 programming:
02 RELAY ACTION
STAY CLOSED 2
Enter the relay action as 2 (stay closed).
02 START EVENT
ALARM 1
Enter start and stop events as 1 (alarm).
02 START: ZN LIST
NOT USED 0
Enter 0 (not used) for start and stop zone list.
02 START: ZN TYPE
VIM ACTIVE 65
Enter start zone type 65 (VIM Active).
02 STOP: ZN TYPE
VIM INACTIVE 66
Enter stop zone type 66 (VIM Inactive).
1
2
3
4
5
6
4204
RELAY MODULE
TO CONTROL'S
KEYPAD TERMINALS
+
Ð
TO
TO
BELL
SIREN
RELAY # 2
RELAY # 1