Guardian Technologies N7001V2 Smoke Alarm User Manual


 
Ð 57 Ð
Zone Programming
(continued)
20 INPUT TYPE
RF TRANS. RF:
Note that input types 4 & 5
are valid for certain 5800
series transmitters only
(ex. 5801, 5802, 5802CP).
When using 5700 series
transmitters, always set
the input type to type 3.
The zone number of the
transmitter identifies
whether or not supervision
is required (ex. 5700
wireless zone number 63 is
not supervised).
Enter the device type as follows: 0=device not used;
1=hardwired; 3=supervised RF transmitter (RF);
4=unsupervised RF transmitter (UR); 5=RF button
type transmitter (BR); 6=serial number polling loop
device (SL); 7=DIP switch type polling loop device
(DP); 8=right loop of DIP switch type device (PS).
Right loops refer to the use of the right loop on a
4190WH zone expander module and/or 4278 PIR,
which allow hard-wired devices to be monitored by
the polling loop.
If the zone was programmed as input type 1, 7 or 8,
the summary display appears. The display will then
repeat with the zone number question for
programming the other zones in the system. Enter
00 to exit back to normal programming mode.
20 LOOP NUMBER
OR
20 LEARN S/N ?
1=YES 0=NO
If this is a previously "enrolled" sensor, the loop
number for this zone will appear. Press [*] to
continue.
If the sensor's serial number has not been
"enrolled," the serial number can be enrolled now by
entering 1, or it can be enrolled later by using the
ÒSerial Number Enrolling/DeletingÒ menu (see next
section). Enter 0 if serial number will be enrolled
later. The summary screen will then appear (see
summary screen description on previous page).
20 INPUT S/N : L
A000-0000: 1
If enrolling the serial number now (entering 1 at the
last prompt), this prompt appears. You can enroll
transmitter serial numbers using either of two
methods.
A. Fault the transmitter two times. The keypad will
beep twice when it hears each transmission.
When enrolling transmitters assigned as BR
input type (e.g. 5802, 5802CP), allow 8 seconds
between transmissions.
OR
B. Enter the serial number directly from the keypad.
The serial number is located on the bar code
label of the transmitter. Simply enter the 7-digit
number following the letter "A" then press [*].
Enter the appropriate loop number for the zone
being programmed and press [*].
When the serial number has been successfully
enrolled, its number appears in the display. A typical
display is shown below:
20 PROG AS RF:1
A001-3078:1
Press [*] to continue. The summary screen will then
appear (see summary screen description on
previous page).