Carrier 48/50PD05 Air Conditioner User Manual


 
94
Table 50 — Fan Performance - 48PDD05 Horizontal Units
AIRFLOW
(Cfm)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1200
436 0.12 559 0.19 661 0.27 753 0.35 839 0.45
1300
456 0.14 574 0.22 673 0.30 762 0.39 845 0.49
1400
477 0.17 592 0.25 687 0.34 774 0.43 853 0.53
1500
500 0.20 611 0.29 703 0.38 787 0.48 864 0.58
1600
523 0.24 631 0.33 721 0.43 801 0.53 877 0.63
1700
548 0.28 652 0.38 739 0.48 818 0.58 891 0.69
1800
573 0.32 674 0.43 759 0.54 835 0.64 906 0.76
1900
600 0.37 697 0.48 779 0.60 854 0.71 923 0.83
2000
627 0.43 720 0.55 801 0.67 873 0.79
941 0.91
AIRFLOW
(Cfm)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1200
918 0.54 993 0.64 1063 0.75 1130 0.86 1193 0.97
1300
922 0.58 995 0.69 1064 0.80 1130 0.91 1193 1.03
1400
929 0.63 1000 0.74 1067 0.85 1132 0.97 1194 1.09
1500
937 0.69 1006 0.80
1072 0.91 1136 1.03 1196 1.16
1600
947 0.74 1015 0.86 1079 0.98 1141 1.10 1201 1.23
1700
959 0.81 1025 0.93 1088 1.05 1148 1.18 1207 1.31
1800
973 0.88 1037 1.00 1098 1.13 1157 1.26 1214 1.39
1900
988 0.95 1050 1.08 1110 1.21 1168 1.35 1223 1.48
2000
1004 1.04 1065 1.17 1123 1.30 1179 1.44 1234 1.58
LEGEND
Bhp -- BrakeHorsepower
__ High--RangeMotor/DriveRequired
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
Table 51 — Fan Performance -- 48PDE05 Horizontal Units
AIRFLOW
(Cfm)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1200
443 0.12 564 0.20 666 0.27 758 0.36 842 0.45
1300
463 0.15 580 0.22 678 0.31 767 0.40 849 0.49
1400
485 0.17 598 0.26 693 0.34 778 0.44 858 0.54
1500
508 0.21 617 0.30 709 0.39 792 0.48 869 0.59
1600
532 0.24 638 0.34 727 0.43 807 0.54 882 0.64
1700
558 0.28 660 0.39 746 0.49 824 0.59 896 0.70
1800
584 0.33 682 0.44 766 0.55 842 0.66 912 0.77
1900
611 0.38 706 0.50 788 0.61 861 0.72 930 0.84
2000
639 0.44 731 0.56 810 0.68 882 0.80
948 0.92
AIRFLOW
(Cfm)
AVAILABLEEXTERNALSTATICPRESSURE(in.wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1200
922 0.55 996 0.65 1066 0.75 1133 0.86 1196 0.97
1300
926 0.59 999 0.69 1068 0.80 1133 0.92 1196 1.03
1400
933 0.64 1004 0.75
1071 0.86 1136 0.98 1197 1.10
1500
942 0.69 1011 0.80 1077 0.92 1140 1.04 1200 1.17
1600
952 0.75 1020 0.87 1084 0.99 1146 1.11 1205 1.24
1700
965 0.82 1030 0.94 1093 1.06 1153 1.19 1211 1.32
1800
979 0.89 1043 1.01 1104 1.14 1163 1.27 1220 1.41
1900
995 0.97 1057 1.09 1116 1.22 1174 1.36 1229 1.50
2000
1012 1.05 1072 1.18 1130 1.32 1186 1.46 1240 1.60
LEGEND
Bhp -- BrakeHorsepower
__ High--RangeMotor/DriveRequired
NOTES:
1. Maximum continuous BHP is 2.0.
2. See General Fan Performance Notes.
48/50PD