Carrier 48/50PD05 Air Conditioner User Manual


 
69
APPENDIX A - LOCAL DISPLAY AND CCN TABLES (CONT)
Table 27 — MODE - RUN STATUS (con t)
ITEM EXPANSION RANGE UNITS
CCN
TABLE/SUB---TABLE
CCN POINT
CCN WRITE
STATUS
STRT Component Starts
A1 Compressor A1 Starts xxxxxx ST_A1 forcible
CCH Crankcase Heater Starts xxxxxx ST_CCH forcible
IDF Indoor Fan Starts xxxxxx ST_IDF forcible
OFC.1 Outdoor Fan 1 Starts xxxxxx ST_OFC_1 forcible
HT.1 Heat Stage 1 Starts xxxxxx ST_HTR_1 forcible
HT.2 Heat Stage 2 Starts xxxxxx ST_HTR_2 forcible
PE.1 Power Exhaust 1 Starts xxxxxx ST_PE_1 forcible
PE.2 Power Exhaust 2 Starts xxxxxx ST_PE_2 forcible
ALRM Alarm Relay Starts xxxxxx ST_ALM forcible
(ALRMDISP) = CCN
only)
ALRMDISP
Active Alarm 1 Code xxx ALMCODE1
Active Alarm 2 Code xxx ALMCODE2
Active Alarm 3 Code xxx ALMCODE3
Active Alarm 4 Code xxx ALMCODE4
Active Alarm 5 Code xxx ALMCODE5
Reset All Current Alarms Yes/No ALRESET forcible
Reset Alarm History Yes/No ALHISCLR forcible
(GENERIC = CCN
only)
GENERIC
up to20 points
(LON_DATA = CCN
only)
LON_DATA
nviSpaceTemp xxx.x dF NVI_SPT forcible
nviSetPoint xxx.x dF NVI_SP forcible
nvoSpaceTemp xxx.x dF NVO_SPT
nvoUnitStatus.mode xxxx NVO_MODE
nvoUnitStatus.heat_out_p xxx.x % NVO_HPRI
nvoUnitStatus.heat_out_s xxx.x % NVO_HSEC
nvoUnitStatus.cool_out xxx.x % NVO_COOL
nvoUnitStatus.econ_out xxx.x % NVO_ECON
nvoUnitStatus.fan_out xxx % NVO_FAN
nvoUnitStatus.in_alarm xxx NVO_ALRM
nviSetPtOffset xxx.x ^F NVI_SPTO forcible
nviOutsideTemp xxx.x dF NVI_OAT forcible
nviOutsideRH xxxx.x % NVI_OARH forcible
nvoEffectSetPt xxx.x dF NVO_EFSP
nvoOutsideTemp xxxx.x dF NVO_OAT
nvoOutsideRH xxx.x % NVO_OARH
nviSpaceRH xxx.x % NVI_SPRH forcible
nviCO2 xxxxx NVI_CO2 forcible
nvoCO2 xxxxx NVO_CO2
nvoTEMP1 xxx.x dF NVO_SAT
nvoTEMP2 xxx.x dF NVO_RAT
nviPCT1 xxx.x % NVI_RHSP forcible
nvoPCT1 xxx.x % NVO_SPRH
nviDISCRETE1 Off/On NVI_FSD forcible
nviDISCRETE2 No/Yes NVI_OCC forcible
nviDISCRETE3 Off/On NVI_IAQD forcible
nvoDISCRETE1 Off/On NVO_FSD
nvoDISCRETE2 No/Yes NVO_OCC
nvoDISCRETE3 Off/On NVO_IAQD
nciCO2Limit xxxxx NCI_CO2 forcible
nciSetPnts.occupied_cool xxx.x dF NCI_OCSP forcible
nciSetPnts.standby_cool xxx.x dF NCI_SCSP forcible
nciSetPnts.unoccupd_cool xxx.x dF NCI_UCSP forcible
nciSetPnts.occupied_heat xxx.x dF NCI_OHSP forcible
nciSetPnts.standby_heat xxx.x dF NCI_SHSP forcible
nciSetPnts.unoccupd_heat xxx.x dF NCI_UHSP forcible
48/50PD