Sensor Trim
Corrective offsets can be applied to the space temperature and the
supply air temperature sensor readings. These corrections are set in
the ConfigurationTRIM menu for the display, or in the
MaintenanceTRIM table for CCN. See th e Indoor Air Quality
section for available adjustments to IAQ and OAQ sensor readings.
The space temperature may be corrected by entering either a
calibration temperature value in SPT.C, or an offset temperature
value in SPT.T. The supply-air temperature may be corrected by
entering either a calibration temperature value in SAT.C,oran
offset temperature value in SAT.T. The return--air temperature may
be corrected by entering either a calibration temperature value in
RAT.C or an offset temperature value in RAT.T. Temperature
corrections should only be made if sensor readings are compared to
an accurate reference temperature measurement device.
Transducer Troubleshooting
The electronic control uses suction pressure transducers to measure
the suction pressure of the refrigerant circuits. The pressure/voltage
characteristics of these transducers are in shown in Table 18, the
5vdc power is applied to legs A and B of the transducer and legs B
to C represent the voltage drop shown in the table. The accuracy of
these transducers can be verified by connecting a n accurate
pressure gauge to the second refrigerant port in the suction line.
Forcing Inputs and Outputs
Many variables may have th eir value forced through CCN or
directly at the local display. This can be useful during diagnostic
testing and also during operation, typically as part of an advanced
third party control scheme. Input and output points that may be
forced are i ndicated as ‘forcible’ i n the write status column of the
display and CCN tables.
If the user needs to force a variable, follow the same process as
when editing a configuration parameter. A forced variable will be
displayed on the Scrolling Marquee with a blinking period “.”
following its value. A forced value on Navigator accessory is
indicated with a blinking “f”. A forced value on CCN devices is
indicated with “Control” if forced at the unit display, or
“Supervisor” if forced via CCN. To remove a local force with the
Scrolling Marquee, select the point with the ENTER key and then
press the up--arrow and down-arrow keys simultaneously.
IMPORTANT: In the case of a control power reset, any force in
effect at the time of power reset will be cleared.